Modulating valve with supported producut diaphragm
APV DELTA RGMS4 - MFS + MFH ATEX
Instruction manual UK-1
APV
3. Identification of valve,
Temperature classes, Responsibilities
3.1.
Identification of valves for use in ATEX environment
ATEX - identification:
-
Equipment group II
-
Equipment category
outside 2G
inside no equipment
- Explosion subcategory IIB
Ambient temperature for the operation
0 °C ≤ T
amb
≤ 40 °C
- temperature classes TX (according to table 3.2)
3.2.
Temperature classes and permissible temperatures
Media temperature
≤ 75 °C
≤ 95 °C
≤ 130 °C
up to
140 °C
= Tmax.
Safety addition
+ 5 °C
+ 5 °C
+ 5 °C
+ 5 °C
Temperature class
T6
T5
T4
T3
Under standard operating conditions the highest surface
temperature will be comparably as high as the temperature of the
medium (product and cleaning liquid) plus a safety addition for local
temperature increases. The valve must be completely free to the
environment in order to provide for sufficient heat release.
All data (temperature classes) refer to an ambient temperature
of 0°C to 40°C. If the ambient temperature is above 40°C, the
temperature difference must be adjusted. In all cases, contact your
responsible SPX FLOW representative!