6. Electronic module
6.1.1 Switch-over of feedback signals
The signals to the control can be switched over via the bridge
between the terminals 10, 11 and 12.
If a bridge is located between the terminals 10 and 11 (normal), the
signal is transferred from sensor 1
(closed valve position)
to input
DI0 of the control. The signal of sensor 2
(open valve position)
is
sent to input DI1.
In case of a bridge between terminals 11 and 12 (reverse), the
signal of sensor 1
(closed valve position)
is sent to input DI1
of the control. At input DO0, the signal of sensor 2
(open valve
position)
switched.
If there is no bridge between the terminals 10, 11 and 12, this will
lead to an error message.
The two LEDs
'valve open'
and
'valve closed'
will flash in this
case.
6.2.
Functional description of connections
Terminal
Designation
Functional description
for all valve types
Funtional description
for D4, D4 SL and DA4 valve types
1
AS-i +
AS-i network connection
AS-i network connection
2
AS-i -
AS-i network connection
AS-i network connection
3
5 VDC
voltage supply for valve sensor
voltage supply for valve sensor
4
Sensor 1
sensor signal 1
(closed valve position)
connection Hall sensor 3
(closed valve position)
5
GND
ground for sensor supply
6
5 VDC
voltage supply for valve sensor
voltage supply for valve sensor
7
Sensor 2
sensor signal 2
(open valve position)
connection Hall sensor 2
(open valve position)
8
GND
ground for sensor supply
ground for sensor supply
10
Normal
normal allocation of feedback signals
normal allocation of feedback signals
11
Feedback
tie point for cable bridge
tie point for cable bridge
12
Reverse
reverse allocation of feedback signals reverse allocation of feedback signals