Maintenance Schedule

Maintenance Service

Monthly

Semi-annually

Seasonal Startup or annually

Inspect General Condition and Operation

x

x

Observe Operation of:

Mechanical–motor, pump, fan and drive mechanism

x

x

Makeup valve (if equipped)

x

x

Inspect for unusual noise or vibration

x

x

inspect and Clean:

Air inlet

x

x

PVC drift eliminators

x

x

Distribution system and nozzles

x

x

Collection basin

x

x

Fan and pump motor exterior

x

x

Coil surface

x

Check:

Collection water basin level

x

x

Blowdown–adjust as required

x

x

Lube lines if equipped:

Check for leaks in hoses or fittings

x

R

x

Belt drive:

Fan shaft bearing lubrication (every 3 mo.)

every 3 months

every 3 months

Check and tighten support fasteners

x

Check shaft, sheave and belt alignment

x

Check belt tension and condition

x

x

Check sheave bushing fastener torque

x

Fan:

Check fan assembly fasteners

x

Motor:

Lubricate (grease as required)

R

Check mounting bolts for tightness

x

Operate at least

3 hours a month

3 hours a month

3 hours a month

Basin Heater (if equipped):

Check for proper operation of temp/low water level sensor

x

Inspect/clean buildup of contaminant from sensor

x

x

Structure:

Inspect/tighten all fasteners

x

x

Inspect and touch up all metal surfaces

x

R

 — Refer to Component User Manual

Note:

  It is recommended at least weekly, that the general operation and condition be observed. Pay 

attention to any changes in sound or vibration that may signify a need for closer inspection.

Содержание Hexacool Air Cooled Condenser none

Страница 1: ...Marley MC Fluid Cooler User Manual uk_07 1185C...

Страница 2: ......

Страница 3: ...n and operation of your fluid cooler Carefully read the manual before installation or operation of the fluid cooler and follow all instructions Save this manual for future reference Indicates presence...

Страница 4: ...plate located on the access door Safety First The location and orientation of the fluid cooler can affect the safety of those responsible for installing operating or maintaining the fluid cooler Howev...

Страница 5: ...s possible to promote ease of maintenance and to permit freedom of airflow into and through the fluid cooler If you have questions about the adequacy of the available space and the intended configurat...

Страница 6: ...ure reference and maintenance purposes Hoisting Fluid Cooler All MC Fluid Cooler models consist of two modules per cell The upper module includes hoisting clips at the bottom corners Hoisting clips on...

Страница 7: ...ule skid and beams and from the top of the bottom module Apply the mastic sealing strip supplied with the fluid cooler according to the MC Fluid Cooler Field Installation Drawing instructions Place to...

Страница 8: ...ire motor leads as shown on the motor nameplate matching the supply voltage Do not deviate from the motor nameplate wiring Either of following symbols may be shown on the motor nameplate Y or YY These...

Страница 9: ...ps Motor rotation must be the same in both VFD mode and By pass mode If cable distance between the VFD and motor is greater than 31m a DV DT output filter is recommended to avoid damage to the motor 3...

Страница 10: ...jury Failure to correctly install the VFD drive will automatically void all warranties associated with the motor and any equipment that is either electrically or mechanically directly attached to the...

Страница 11: ...ally and observe the action of the sheaves and belts to be sure that the motor is properly aligned with the fan sheave See Belt Tensioning and Sheave Alignment on page 21 2 Momentarily bump energize t...

Страница 12: ...ntil the water reaches a level approximately 4mm below the lip of the overflow 4 Start your pump s and check for proper rotation as indicated by the arrow on the pump cover observe system operation A...

Страница 13: ...r operating the fluid cooler fan After biocidal pretreatment has been successfully completed cooling water may be circulated over the tower with the fan off Whenbiocidaltreatmenthasbeenmaintainedatasa...

Страница 14: ...cycled to control process fluid temperature Doing so may result in excessive and premature scaling on the coil exterior surface It is recommenced that while process fluid is being circulated through t...

Страница 15: ...lies to all 7055 and 7075 MC Fluid Cooler models Multicell fluid coolers equipped with two speed motors will maximize energy savings and minimize sound levels if fans are staged so that all fans are b...

Страница 16: ...luid cooler it causes the falling water to be drawn inward Thus under fan operation the lower periphery of the fluid cooler structure remains partly dry seeing only random splash ing from within the f...

Страница 17: ...nt heat load on the process fluid Fluid exiting the coil must be maintained at or above 8 C Cycling of the recirculation pump should not be used to control process temperatures Draining the coil is no...

Страница 18: ...0 with hardness and alkalinity levels between 100 and 300 ppm expressed as CaCO3 Chlorine if used shall be added intermittently with a free residual not to exceed 1 ppm maintained for short periods E...

Страница 19: ...year The drift eliminators easily accessible surfaces and the coil should be flushed by use of a moderate pressure water nozzle being careful not to cause physical damage A reliable water treatment p...

Страница 20: ...he makeup water assuming none of the solids form scale or are otherwise removed from the system When water treatment chemicals are added they should not be in troduced into the circulating water syste...

Страница 21: ...tioned as close as possible to the motor in order to minimize torque on the motor bushings The motor and fan sheaves may have grooves that are not used The bottom surface of the motor and fan sheaves...

Страница 22: ...of vibration Abnormal aspects relating to the rotating equipment should be considered reason to shut down the fluid cooler until the problem can be located and corrected Observe operation of the moto...

Страница 23: ...he recirculation water system be drained Leave the basin drains open Draining the coil is not recommended draining promotes corro sion inside the coil tubes See protecting coil in Freezing weather on...

Страница 24: ...olts and tighten as required Do not start motor before determining that there will be no interfer ence with free rotation of the fan drive The motor s should be operated for three hours at least once...

Страница 25: ...shipped within 24 hours by air freight if necessary However you would obviously benefit from anticipating your need in ad vance thus avoiding the cost of special handling Be sure to mention your flui...

Страница 26: ...ion every 3 mo every 3 months every 3 months Check and tighten support fasteners x Check shaft sheave and belt alignment x Check belt tension and condition x x Check sheave bushing fastener torque x F...

Страница 27: ...ments contain important information relating to safe installation and operation of the fluid cooler Field installation is required for some optional accessories A separate installation drawing or manu...

Страница 28: ...nstall or replace fan Motor runs hot Wrong voltage or unbalanced voltage Check voltage and current of all three lines against nameplate values Wrong motor RPM Check nameplate against power supply Chec...

Страница 29: ...e is above design Check to see if local heat sources are affecting fluid cooler See if surrounding structures are causing recirculation of tower discharge air Discuss remedy with Marley representative...

Страница 30: ......

Страница 31: ......

Страница 32: ...3 8AB UNITED KINGDOM 44 0 1905 720 200 info uk spx com spxcooling com In the interest of technological progress all products are subject to design and or material change without notice 2008 SPX Coolin...

Отзывы: