SPX Cooling Technologies 92-1322C Скачать руководство пользователя страница 9

     

9

Testing above Freezing Temperatures

Under  normal  operating  conditions  the  heaters  will  be  turned  on  at  a 
water temperature between 40° and 45°F, and turned off when the water 
temperature exceeds 45°F. For testing the system at temperatures above 
45°F there are two methods as follows:

Method A

1. Disconnect power to the control panel using standard lockout proce-
dure for safety.

2. Remove the panel cover

3. Remove the sensor wires connected to terminals T1 and T2 on the 
relay circuit board.

SOLID STATE RELAY CARD

PROBE

BASIN

RED

CT

N

G2
G1
T2
T1
SH

120

RED

240

24

COM

NC NO

BLK

RED

BLK

SHIELD

RESISTOR

GREEN

Figure 2

/  Operation  /

4.  Connect  a  1.5K  ohm  resistor  (included  in  panel)  across  T1  and  T2 
terminals—see 

Figure 2

.

5.  Replace  panel  cover  and  verify  probe  is  submerged  in  tower  basin 
water.

6. With panel cover in place turn on power supply to the system. An au-
dible CLICK should be heard as the contactor engages. If this does not 
happen, refer to the Troubleshooting section of this manual.

7. If the system tests OK turn off power, remove the panel cover and re-
move the resistor. Replace sensor wires T1 and T2 and replace the cover. 
Turn system on.

 

Содержание 92-1322C

Страница 1: ...Marley Electric Basin Heater User Manual 92 1322C...

Страница 2: ......

Страница 3: ...e freight carrier 2 Check the nameplate on the enclosure and verify that the heaters and the control panel are rated for the correct voltage 3 Check the watt rating on each element and verify the sum...

Страница 4: ...olid state relay card to detect low temperature and low water conditions The panel enclosure is rated NEMA 4X liquid tight noncorrosive and the sensor cable is UL outdoor rated The sensor probe is sta...

Страница 5: ...perate out of the water It would become extremely hot 1500 F and destroy the heater element and or ig nite nearby combustible materials As a precaution and to prevent fires when the clearance between...

Страница 6: ...Eithercomputetheactualloadontheheatercontrol panel to determine the sum total KW of all the heaters connected to it or use the nameplate rating to determine the wire size required To calculate amp dra...

Страница 7: ...embly is factory installed to the control panel Do not at tempt to lengthen or shorten the cord Sensor assemblies with various lengths up to 99 0 are available and may be specified at the time of purc...

Страница 8: ...evel above the sensor probe and temperature above 45 F both these LEDs will be off If the red LED is illuminated this indicates a low water condition and the heaters will not operate If the green LED...

Страница 9: ...lay circuit board SOLID STATE RELAY CARD PROBE BASIN RED CT N G2 G1 T2 T1 SH 120 RED 240 24 COM NC NO BLK RED BLK SHIELD RESISTOR GREEN Figure 2 Operation 4 Connect a 1 5K ohm resistor included in pan...

Страница 10: ...ke sure water still covers the heater elements 3 Place the probe in a container of ice water making sure both metal parts of the probe are submerged but not the cord 4 Energize the heater control pane...

Страница 11: ...hese procedures 1 Disconnect power to the control panel using standard lockout proce dures for safety 2 Remove the panel cover 3 Install a jumper wire between relay terminals G1 and G2 see Figure 3 Op...

Страница 12: ...the heaters are energized A If the red LED is on and the sensor probe is submerged in water no ice this indicates the sensor probe is defective Confirm by discon necting power and placing a jumper acr...

Страница 13: ...ided See Figure 2 If the system now works the sensor probe is defective and must be replaced If the system does not work go to step 2 2 Reconnect power and take a voltage reading across N and 24 240 o...

Страница 14: ...D 4 Sensor Probe with 12 cord A81137D Sensor Probe with 22 cord B07688D contact Marley for other cord lengths 5 Heater Element contact Marley for specific heater elements Replacement Parts Call your M...

Страница 15: ......

Страница 16: ...213 UNITED STATES 913 664 7400 spxcooling spx com spxcooling com In the interest of technological progress all products are subject to design and or material change without notice 2008 SPX Cooling Tec...

Отзывы: