/  Installation  /

Control Panel

The control panel is suitable for outdoor mounting, and may be mounted 
on the tower, but not inside the tower. Wire the heaters to the panel. Wire 
the panel to the branch circuit supplying power to the heater.

The field supplied branch circuit disconnect switch and the branch circuit 
protective device (fusing or circuit breaker) shall be sized in accordance 
with  the  NEC/CEC  rules  for  actual  load.  The  total  heater  load  can  be 
calculated as shown below.

If the heater control panel is furnished with an optional disconnect, in-
stallation  of  the  panel  in  relationship  to  the  heater  element  shall  be  in 
accordance with the NEC/CEC rules.

The main incoming conduit hub and the main power termination points are 
sized for total nameplate KW and voltage. The actual load for a particular 
installation may be less. Either compute the actual load on the heater control 
panel to determine the sum total KW of all the heaters connected to it or 
use the nameplate rating to determine the wire size required. To calculate 
amp draw for a particular installation use the following formulas:

Should water be drained, either intentionally or accidentally, from 
the basin, the basin heater MUST be checked manually to insure the 
power source to the heating element is OFF. Although equipped with 
a low liquid level sensor probe, contaminants on or around the probe 
may cause false readings allowing the element to remain energized 
under low or no water conditions. Do not re-energize the unit until 
the sensor probe is fully submerged in water.

IF THE UNIT IS ENERGIZED WHILE THE SENSOR PROBE IS NOT 
FULLY SUBMERGED IN WATER, COMBUSTION/FIRE MAY RESULT, 
WHICH COULD DAMAGE OR DESTROY THE TOWER AND MAY CAUSE 
DAMAGE TO PERSONS OR PROPERTY NEARBY.

KW 

x

 1000

Voltage

=

 Amperage for Single Phase Applications

KW 

x

 1000

1.7312 

x

 Voltage

=

 Amperage for Three Phase Applications

or

 

Caution

Содержание 92-1322C

Страница 1: ...Marley Electric Basin Heater User Manual 92 1322C...

Страница 2: ......

Страница 3: ...e freight carrier 2 Check the nameplate on the enclosure and verify that the heaters and the control panel are rated for the correct voltage 3 Check the watt rating on each element and verify the sum...

Страница 4: ...olid state relay card to detect low temperature and low water conditions The panel enclosure is rated NEMA 4X liquid tight noncorrosive and the sensor cable is UL outdoor rated The sensor probe is sta...

Страница 5: ...perate out of the water It would become extremely hot 1500 F and destroy the heater element and or ig nite nearby combustible materials As a precaution and to prevent fires when the clearance between...

Страница 6: ...Eithercomputetheactualloadontheheatercontrol panel to determine the sum total KW of all the heaters connected to it or use the nameplate rating to determine the wire size required To calculate amp dra...

Страница 7: ...embly is factory installed to the control panel Do not at tempt to lengthen or shorten the cord Sensor assemblies with various lengths up to 99 0 are available and may be specified at the time of purc...

Страница 8: ...evel above the sensor probe and temperature above 45 F both these LEDs will be off If the red LED is illuminated this indicates a low water condition and the heaters will not operate If the green LED...

Страница 9: ...lay circuit board SOLID STATE RELAY CARD PROBE BASIN RED CT N G2 G1 T2 T1 SH 120 RED 240 24 COM NC NO BLK RED BLK SHIELD RESISTOR GREEN Figure 2 Operation 4 Connect a 1 5K ohm resistor included in pan...

Страница 10: ...ke sure water still covers the heater elements 3 Place the probe in a container of ice water making sure both metal parts of the probe are submerged but not the cord 4 Energize the heater control pane...

Страница 11: ...hese procedures 1 Disconnect power to the control panel using standard lockout proce dures for safety 2 Remove the panel cover 3 Install a jumper wire between relay terminals G1 and G2 see Figure 3 Op...

Страница 12: ...the heaters are energized A If the red LED is on and the sensor probe is submerged in water no ice this indicates the sensor probe is defective Confirm by discon necting power and placing a jumper acr...

Страница 13: ...ided See Figure 2 If the system now works the sensor probe is defective and must be replaced If the system does not work go to step 2 2 Reconnect power and take a voltage reading across N and 24 240 o...

Страница 14: ...D 4 Sensor Probe with 12 cord A81137D Sensor Probe with 22 cord B07688D contact Marley for other cord lengths 5 Heater Element contact Marley for specific heater elements Replacement Parts Call your M...

Страница 15: ......

Страница 16: ...213 UNITED STATES 913 664 7400 spxcooling spx com spxcooling com In the interest of technological progress all products are subject to design and or material change without notice 2008 SPX Cooling Tec...

Отзывы: