Enviro Maintenance Manual 2004 

TROUBLE SHOOTING 

I. 

Exhaust fan does not run. 

Reset the system once.  Press the reset button in the LV10 J-Box or turn the fan selector switch 
to “OFF” and “ON”.  Observe the sequence that follows. 

1.The fan does not start and there is no indication on remote panel. 

 

a)Check power from the breaker to the RPD10. 
b)Check the three wiring connection from the wash panel to the RPW10 panel. 

 

2.The fan does not start but the green normal pilot energizes for 30 seconds goes 

out and “Filter removed” pilot energizes. 

a)Check wiring between KES filter box LV10 J-box terminals 5 & 4 and the KESF fan motor 

starter.  

b)Check wiring between the RPD10 or RPW10 remote and the KES-ISH LV10 J-Box 
c)Reset the exhaust fan overload in the exhaust fan motor starter on the KESF fan section. 
d)Check three phase power to the KESF fan section disconnect. 
e)Check if exhaust duct access door is open between the KES filter section and hood. 
f)Check that all filters on in place. 
g)Check if the prefilter or box filter access door on the KES unit is open 
h)Check the Filter Removed pressure switch.  The switch must make and close after 30 

seconds of operation.  Adjust the pressure setting or replace switch. 

i)If all the filters are in place check if pressure tips on the end of the pressure switch 

manifolds are plugged.  There is a pressure tip in front and behind each filter. 

j)Measure Exhaust air volume.  If low increase fan RPM to within FLA of fan motor 
k)Check KESF exhaust fan motor starter coil.  Replace or repair. 
l)Check KESF fan belts if loose or broken. 
m)Check KESF exhaust fan motor.  Replace or repair. 

3.The exhaust fan runs for 30 seconds then shuts off and one of the Filter 

Clogged pilots energizes. 

a.Check the wiring from the LV10-J-Box to the pressure switch 
b.Check pressure switch operation P1, P2 & P3.  These switches should remain open after 

30 seconds operation.  Calibrate the pressure setting or replaced switch. 

c.Check the wiring between the RPD10 or RPW10 panel and the LV10 J-Box. 

 

II. 

Low Exhaust Air 

1.Exhaust fan is running but exhaust air is low.  

a)Check if fan belts are slipping.  Tighten if necessary. 
b)Check if fusible link fire damper has closed in the KES filter section.  Replace fusible link. 
c)Check if filters are dirty but have not activated the “Filter Clogged” pilot.  Replace dirty 

filters. 

d)Check for correct fan rotation. 

Содержание KES Enviro

Страница 1: ...KES Enviro Maintenance Manual ___________________________ Spring Air Systems Inc Oakville Ontario Phone 905 338 2999 Fax 905 338 0179 info springairsystems com...

Страница 2: ......

Страница 3: ...or AP MP Panels 4 Filter Hood or Dry Grease Extractor 5 Control Circuit 7 Setting the Day and Time 13 Setting the Weekday Fan ON and OFF Times 14 Setting Weekend Operation 15 Odor Spray Systems 15 Whe...

Страница 4: ......

Страница 5: ...ries Inc UL listing allows the kitchen exhaust air to be discharge to atmosphere at low levels Prior to any installation the installer must seek approval from the authorities having jurisdiction THE S...

Страница 6: ...L E C T R I A L W I R I N G A N D N A T I O N A L C O D E R E Q U I R E M E N T S S H A L L C O N F O R M T O A L L L O C A L N O T E 1 I N T E R N A L W I R I N G B Y S P R I N G A I R C U R C U I T...

Страница 7: ...S TO THE WET CHEMICAL SWITCH 120V 1 60 1 AMP MOTORIZED INLET DAMPER AND END OPTIONAL THREE 3 WIRES TO OPTIONAL POWER SUPPLY TO SUPPLY FAN MOTOR STARTER 120V 1 60 2 AMPS DRY CONTACT FOR BUILDING FIRE A...

Страница 8: ...ses and sends power through terminals 3 4 to the RPW10 remote panel to energize the exhaust fan through terminals 5 4 in the LV 10 J Box The LV10 J Box is mounted on the KES ISH filter section The NOR...

Страница 9: ...1 2 ESC OK 1 Q 3 1 Q 1 1 2 Q4 1 2 Q2 15 AMP CURCUIT BREAKER AUX FAN SWITCH I4 I2 L N I1 I3 01 20 03 Mo 09 00 I 5 I 6 I7 I8 L N OVERIDE SWITCH OFF ON RPD10A ELECTRICAL DATA I 1 I 2 I 3 I 4 RUN STOP BOX...

Страница 10: ...Internal Wiring Figure 10 REMOVED WARNING CLOGGED BOX FILTER FILTER OVERIDE BAG FILTER CLOGGED PREFILTER CLOGGED NORMAL FIRE IN PANEL BACK HOLES LOCATED PANEL MOUNTING KES OFF ON FILTER 8 0 14 0 5 RPD...

Страница 11: ...C P4 BAG FILTER REMOVED SWITCH COPPER TUBING REMOVED SWITCH SECTION TO RIGHT OF BOX FILTER ACCESS DOOR PRESSURE SWITCHES LOCATED ON KES ISH FILTER BOX P5 B A G P4 P 3 P2 PREFILTER P 1 Pressure Switch...

Страница 12: ...P4 BAGFILTERS SETAT0 25 W C L1 O L L2 L3 T1 T3 T2 A1 A2 6 3 7 M1 WIRINGHARNESSIN MOTOR STARTER THREE WIRES FROM LV10 PANEL TO EXHAUST FAN MOTOR STARTER BY MECHANICAL WHEN KES FAN AND FILTER SECTIONS A...

Страница 13: ...he KES unit or within the KES unit a firestat located at the inlet of the KES filter section is activated When the exhaust air reaches 160 F the firestat is energized The exhaust fan shuts off the NOR...

Страница 14: ...osition Figure 17 System Reset After any of the safety circuit annunciation the system must be reset The system is reset by toggling the RESET switch in the LV10 J box or switching the OVERRIDE SWITCH...

Страница 15: ...Enviro Maintenance Manual 2004 RPD10 Face Plate Figure 19 RPW10 Face Plate Figure 20...

Страница 16: ...3 7 1 3 6 95 G1 96 T 3 A2 L3 A1 T1 KES TELE MOTOR STARTER INEEMAC4ENCLOSURE MOUNTED ON FAN UNIT L1 EEMAC4 M1 T 1 O L L1 FILTER REMOVED SWITCHES EXHAUSTINLETSETAT225 F HI TEMP STAT LOCATED IN THE P5 BO...

Страница 17: ...01 00 Th 00 00 Su 06 16 01 01 00 MM DD YY Set Clock Set Clock MM DD YY 01 01 00 Th 00 00 Set Clock Su 00 00 01 01 00 MM DD YY Prg Name Set Clock Set Parma Set Clock Set Parma Prg Name Stop to return...

Страница 18: ...Press to remove Monday from the weekly schedule The dash indicates The cursor will move to M Monday 5 The clock has been factory set to turn the fan on at 6 00 a m and off 8 Press to move to the next...

Страница 19: ...ess If your selection is complete press and to return the 9 Press operating screen 10 You have completed programming weekend fan On and Off cycling 01 06 03 Su 06 16 B04 No2 On 10 00 D SS B04 No2 Off...

Страница 20: ...g the setting by is not adequate decrease the cycle to of the original setting If this is not adequate adjust the spray timer B02 a Increase the spray time B02 in increments of 5 seconds After each 5...

Страница 21: ...s are minutes and the two digits to the right are seconds Press to change the cycle length in minutes Press to move to the T 05 00m 9 To change spray time press 11 Press if the cycle time is correct 8...

Страница 22: ...tlet valves are interchangeable Clean them with water When replacing the outlet valve place the new valve in location and note there is a retaining bar near the machine screw hole This retaining bar h...

Страница 23: ...x 24 x 22 V9 4M Class II American Air Filter 24 x 24 x 21 DRI PAK Class II 12 x 24 x 21 DRI PAK Class II Farr Filters 24 x 24 x 22 90 ASHRAE 52 76 Class II 12 x 24 x 22 90 ASHRAE 52 76 Class II BOX F...

Страница 24: ...oved pressure switch The switch must make and close after 30 seconds of operation Adjust the pressure setting or replace switch i If all the filters are in place check if pressure tips on the end of t...

Страница 25: ...pen Replace if necessary V Fire Pilot On 1 The fire stat in the KES filter section exhaust outlet has activated and shut the KES system down If a fire is not present check calibration of firestat TH1...

Страница 26: ...system For heavy cooking applications the bag filters may require replacement every month 4 Odor Spray Option Inspect the odor spray bottle Refill if necessary At startup the odor spray is adjusted t...

Страница 27: ...years of service under most conditions 2 Re greasing of motors depends on the application and is best left to trained service technicians 3 Periodically check if motor is running hotter then normal C...

Страница 28: ...Turn on the Override switch in the RPD10 or RPW10 remote panel The LOGO text message Service Filters within 4 hours will appear Turn FAN OFF switch in the wash panel or remote RPD10 panel to the OFF p...

Страница 29: ...sted With the filters out rotate the pressure adjustment screw slowly clock wise until the unit shuts off Fire Switch Test 41 Jumper terminals 1 16 in the LV10 J Box 42 KES unit shuts off Yes No 43 Fi...

Страница 30: ...nance Manual 2004 FILTER FREQUENCY CHART Enter the date of each filter change Startup date Change No Prefilter Bag Filter Box Filter Odor 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24...

Страница 31: ...ater Wash Cold Water Spray Hot Water Wash Water Wash Control Panels Dry Ventilators REV LOW Hood Filter Hoods Surface Fire Suppression Commercial Kitchen Exhaust Fans Kitchen Enviro Systems KES 100 Ex...

Отзывы: