Spring Air Systems Water Wash Ventilator Maintenance Manual 11/01 

 

Three Sequence Wash Panel Models AP30C and AP30H Electrical 

Figure 8 

 

The detergent water mixture washes the first group of ventilators (up to 50-ft. (15m)).  The wash cycle continues for the 
length of time set on wash timer #1 (T1), adjustable from 0 to 600 seconds.  At the end of wash cycle #1 the blue WASH 
#1” pilot and the hot water solenoid valve #1 shut off and the blue “WASH #2” pilot and hot water solenoid valve #2 
energize.  The detergent and water mixture washes the second group of ventilators (up to 50 ft.  (15m)).  The wash cycle 
continues for the length of time set on wash timer #2, adjustable from 0 to 600 seconds.  At the end of wash cycle #2 the 
blue “WASH #2” pilot  and the hot water solenoid valve #2 shut off and the blue “WASH #3” pilot and the hot water 
solenoid valve #3 energize.  The detergent water mixture washes the third group of ventilators (also up  to 50 ft.  (15 m)).  
At the end of wash cycle #3 the blue “WASH #3” pilot the hot water solenoid valve #3 and the detergent pump shut off.  
The system remains idle until the next time the fan selector switch is rotated to “ON” position. 

FOUR AND FIVE SEQUENCE WASH SYSTEMS 

Four and five sequence wash control panels operate similarly 
to the three-sequence wash.  After the third wash cycle is 
complete the system proceeds to the fourth and fifth wash 
cycles. 

Due to space limitations within the kitchen the four and five 
sequence wash system also have remote solenoid valves.  
The detergent pump and tank are still located in the wash 
control panel.  See wiring and piping diagrams in the back of 
the manual for the four and five sequence wash systems. 

 
 

 

MP40C & MP40H Water Wash Panel 

 

 

     Figure 9 

 

H2

H3

WASH PILOT #3

WASH PILOT #2

HOT WATER SOLENOID #3

HOT WATER SOLENOID #2

B

B

I1

Q: 1 2 3 4  RUN

SMART RELAY

INTERNAL WIRING BY SPRING AIR

I1

SMART RELAY

Q: 1 2 3 4  RUN

H1

Set length

wash here.

and third

of second

B03=WASH3

B02=WASH2

Q1

Q2

I: 1 2 3 4 5 6

L

N

C

N

Set clock

L

B01=WASH1

B04=CLOCK

wash here.

and length
of first

Q1

Q2

Mo  09:00

I: 1 2 3 4 5 6

FAN SWITCH

OFF/AUTO/ON

ALL HOT WATER SOLENOID VALVES
ARE LOCATED REMOTE FROM PANEL

POWER SUPPLY TO THE AP20H/C PANEL
24 HOURS/DAY - 120V/1/60 - 15 AMPS

REMOTE WIRING BY TRADES

POWER TO THE EXHAUST FAN MOTOR STARTER
120V/1/60 - 2 AMPS MAXIMUM.

LV10 PANEL - 120V/1/60 - 2 AMPS MAXIMUM.

(OPTIONAL) POWER SUPPLY TO SUPPLY FAN
MOTOR STARTER - 120V/1/60 - 2 AMPS MAXIMUM

SHUTOFF DAMPER AND END SWITCH 120V/1/60 
2 AMPS MAXIMUM.

POWER TO SHUNT TRIP TO DE-ACTIVATE ELECTRIC

COOKING EQUIPMENT IN THE EVENT OF A FIRE
120V/1/60 - 2 AMPS MAXIMUM.  (SHUNT TRIP OR

POWER TO THE SPRING AIR SYSTEMS ENVIRO FILTER UNIT 

(OPTIONAL) THREE (3) WIRES TO SUPPLY AIR MOTORIZED

RELAY SUPPLIED AND INSTALLED BY ELECTRICAL DIVISION)

DAMPER END SWITCH

REMOTE WIRING FOR ARRANGEMENT "F" & "T" TYPE FIRE DAMPER HOODS

ONLY.  ARRANGEMENT "D" FIRE DAMPER HOODS REQUIRES NO REMOTE WIRING.

ESC

OK

Q3

Q4

I3

I2

I6

I4

I5

HOT WATER SOLENOID #1

WASH PILOT #1

WATER SOLENOID

OPTIONAL COLD

FAN PILOT

B

G

4

1

2

1

2

5

WHITE

RED

1

I6

I4

I3

I2

I5

ESC

OK

Q3

Q4

DETERGENT
PUMP

R5

FIRE TEST

PUMP TEST

8

10

9

R5

4

4

R5

4

4

10

9

4

8

4

9

1

1

2

3

5

4

4

3

1

NORMALLY OPEN

WET CHEMICAL CONTROL

TWO (2) WIRES TO THE

OR

ARRANGEMENT "F" FIRE DAMPERS:
TWO (2) WIRES TO EACH ENS ENCLOSURE LOCATED
AT EACH EXHAUST DUCT COLLAR ON EVERY HOOD

ARRANGEMENT "T" FIRE DAMPER:

AT EACH EXHAUST DUCT COLLAR ON EVERY HOOD

120V/1/60 - 1 AMPS.  WIRE EACH ENS IN PARALLEL.

THREE (3) WIRES TO EACH SOE ENCLOSURE LOCATED

120V/1/60 - 3 AMPS - WIRE EACH SOE IN PARALLEL.

HEAD  120V/1/60 - 1A.

FENWALL DETECTOR

DAMPER SOLENOID

END SWITCH

OR

CURCUIT BREAKER

x x o

x

o

x

o

o

x

Содержание AP10C

Страница 1: ...VENTILATOR MAINTENANCE MANUAL ___________________________ Spring Air Systems Inc Oakville Ontario Phone 905 338 2999 Fax 905 338 0179...

Страница 2: ...d Line Fire Suppression Arrangement T 21 Second Line Fire Suppression Arrangement F 22 Variflow Baffles 23 SB10H One Sequence Wash Plumbing Schematic 24 SBA10C One Sequence Wash Plumbing Schematic 25...

Страница 3: ...l with all the edges ground and polished All ventilators are manufactured to stringent quality standards and are guaranteed to enhance the appearance of any commercial kitchen Model HT B Water wash Ve...

Страница 4: ...water wash D Dry Grease Extractor T Thermostatic Fire Damper F Fusible link spring loaded fire damper D Fusible link dead weight fire damper S Shelf type hood B Box type hood BS Box shelf type hood D...

Страница 5: ...rgized through terminals 4 9 When a motorized damper with end switch is not used in the installation the field electrician must jumper terminals 8 9 in the water wash panel to provide 120V 1 60 power...

Страница 6: ...continues for the period of time set on the wash timer adjustable from 0 to 600 seconds At the end of the wash cycle the blue WASH pilot the detergent pump and the hot water solenoid valve shut off Th...

Страница 7: ...2 4 Hot water solenoid valve 2 H3 4 Hot water solenoid valve 3 OPTIONAL COLD WATER SOLENOID HOT WATER SOLENOID H C FAN PILOT WASH PILOT B PUMP DETERGENT G SMART RELAY Q 1 2 3 4 RUN INTERNAL WIRING BY...

Страница 8: ...systems MP40C MP40H Water Wash Panel Figure 9 H2 H3 WASH PILOT 3 WASH PILOT 2 HOT WATER SOLENOID 3 HOT WATER SOLENOID 2 B B I1 Q 1 2 3 4 RUN SMART RELAY INTERNAL WIRING BY SPRING AIR I1 SMART RELAY Q...

Страница 9: ...Breaker Figure 10 CLEANING THE EXTERIOR Normal soil can be removed with a mild detergent water mixture applied to a cloth To remove baked on grease apply a cleanser to a damp cloth or sponge and rub...

Страница 10: ...WASH SYSTEMS SBA10H SBA10C AP10H AP10C AP20H AP20C AP30H AP30C AP40H AP40C AP50H AP50C The automatic wash control panels are equipped with a solid state microprocessor The fan selector switch is repla...

Страница 11: ...ng until the correct hour appears 4 To change the time press once The hour will be highlighted Press 1 Press these two buttons together Su 11 25 Q 1 2 3 4 I 1 2 3 4 5 6 Su 11 25 Set Clock 11 11 01 MM...

Страница 12: ...bove settings press 4 The clock has been factory set to turn the fan on at 6 00 a m and off to the minute the fan stop in the evening Press to change the minutes to change the hour you want the fan to...

Страница 13: ...the hour that the fan will stop in the evening Press to change the hour you want the fan to stop each evening Press to move to the minute the fan stop in the evening Press to change the minutes to the...

Страница 14: ...minutes 4 The clock has been factory set to turn the fan on at 6 00 a m and off at 23 00 hours or 11 00 p m When the fan shuts off the wash activates To change these times see section Programming the...

Страница 15: ...120V 1 60 2 AMPS MAXIMUM OPTIONAL POWER SUPPLY TO SUPPLY FAN LV10 PANEL 120V 1 60 2 AMPS MAXIMUM POWER TO THE SPRING AIR SYSTEMS ENVIRO FILTER UNIT POWER TO THE EXHAUST FAN MOTOR STARTER DAMPER END SW...

Страница 16: ...secondary coverage as the exhaust air enters the secondary grease extraction chamber The exhaust air continues into the secondary extraction chamber which contains an additional baffle F Residual gre...

Страница 17: ...TYPE RECOMMENDED COOKING USE Type C Medium heavy and heavy duty Mesquites live charcoal Gas charbroilers heavy frying Type H Medium and medium heavy duty Gas charbroilers Fryers Ranges Griddles Most c...

Страница 18: ...ater wash time because of the continuous cold water spray During fan and cooking operation the spray continuously carries grease dirt and lint down the drain which reduces the daily grease build up Th...

Страница 19: ...nstallation Remote wiring and plumbing are shown for an exhaust fan wet chemical systems a Spring Air Systems water wash hood and a SB10H water wash panel In addition to the wiring indicated below pow...

Страница 20: ...1 0 3353 7 3 8 9 40 5 50 0 11 5 3505 7 9 9 7 44 2 54 0 12 0 3658 7 9 9 7 44 2 54 0 12 5 3810 8 5 10 4 47 4 57 9 13 0 3962 8 5 10 4 47 4 57 9 13 5 4115 9 2 11 3 51 4 63 0 14 0 4207 9 2 11 3 51 4 63 0 1...

Страница 21: ...7 1 14 5 4420 17 6 21 5 66 6 81 3 15 0 4772 17 6 21 5 66 6 81 3 Chart No 3 Cold Water Required Model DB Ventilator Length Cold Water Flow USGPM Cold Water Flow l s Ventilator Length Cold Water Flow US...

Страница 22: ...fan motor starter is shut off NOTE The exhaust fan remains on after a primary surface fire suppression system has activated Arrangement D Fusible Link Activated Dead Weight The arrangement D hood and...

Страница 23: ...e wash control panel through terminal 2 Within the water wash control panel the fire relay R5 is energized activating the water wash control panel hood and damper assembly 1 The exhaust fan is shut of...

Страница 24: ...STITUTE FOR THE SURFACE FIRE SUPPRESSION SYSTEM WET CHEMICAL SPRINKLER ETC A SURFACE FIRE PROTECTION MUST BE INSTALLED IN ACCORDANCE WITH APPLICABLE CODES Arrangement F Fusible Link Activated Spring L...

Страница 25: ...ARIFLOW baffles located above a charbroiler are opened to the maximum 450 CFM ft position and the VARIFLOW baffles located above ovens or steamers are closed to the minimum 90 CFM ft position This var...

Страница 26: ...n at about 300 CFM ft The baffles are connected to the Primary baffle on studs fastened by wing nuts There a total of five 5 adjustment positions on each baffle After the water wash hood is installed...

Страница 27: ..._____________________ Spring Air Systems Water Wash Ventilator Maintenance Manual 11 01 25 SBA10C hot water wash cold water spray plumbing Figure 29 MP20C two sequence hot water wash cold water spray...

Страница 28: ..._________________________________________________________ Spring Air Systems Water Wash Ventilator Maintenance Manual 11 01 26 AP30C three sequence hot water wash plumbing Figure 32 MP30H three sequen...

Страница 29: ...T WASH PILOT B PUMP WATER SOLENOID OPTIONAL COLD FAN PILOT G 1 5 INTERNAL WIRING BY SPRING AIR FIRE TEST PUMP TEST I3 FAN SWITCH Q 1 2 3 4 RUN Mo 09 00 I 1 2 3 4 5 6 SMART RELAY Q1 Q2 N L I1 I2 OFF AU...

Страница 30: ...WO 2 WIRES TO EACH ENS ENCLOSURE LOCATED FENWALL DETECTOR DAMPER SOLENOID END SWITCH NORMALLY OPEN OR x x o x o x o o x H2 H3 WASH PILOT 3 WASH PILOT 2 HOT WATER SOLENOID 3 HOT WATER SOLENOID 2 B B I1...

Страница 31: ...check the VORTEX BAFFLE and grease trough for any debris Check that the drain is free and clear SIX MONTHS 1 Clean all line strainers located in the control panel hot water and cold water 2 Check exha...

Страница 32: ...he throat inlet slot of the ventilator Velometer should not exceed three inches in diameter Measuring Exhaust Air Figure 38 PITOT TUBE OR ANEMOMETER Hold the instrument perpendicular to the VORTEX BAF...

Страница 33: ...er drawings 6 Check that all electrical connections are tight and secure 7 Check exhaust duct connections 8 Check that fire damper is open 9 Open ventilator access door and check drain and grease trou...

Страница 34: ...amper only iii Faulty end switch in Fire Damper End Switch Enclosure ENS Arrangement F dampers only iv Fire relay R6 is faulty AP10 SBA10 type only B Blue WASH ON pilot is off i Hot water solenoid val...

Страница 35: ...Air Design CFM Ventilator mounting Height from finished floor to front of hood Make Up Air Systems Good Fair Poor None Hood Item Model Length Width No of Baffles Baffle Size Design CFM Baffle No Left...

Страница 36: ...s in remote hot water piping 14 Water Pressure psi 15 Water temperature F 16 Length of wash minutes 17 Water leaks in ventilator 18 Drain runs clear 19 At the end of the wash 20 Hot water solenoid off...

Страница 37: ...Using your fingers unscrew the diaphragm counter clockwise 5 When replacing old diaphragm with new check to make sure the size of the spacers is the same located under the nut on the diaphragm 6 When...

Страница 38: ...Set Param Set Clock Mo 09 00 Su 09 00 Q 1 2 3 4 or OK 2 Press I 1 2 3 4 5 6 to return to the operating screen until correct year appears Press to move to day until correct day appear Press to until co...

Отзывы: