Spring Air Systems Water Wash Ventilator Maintenance Manual 11/01
6
Three Sequence Wash Panel Models AP30C and AP30H Electrical
Figure 8
The detergent water mixture washes the first group of ventilators (up to 50-ft. (15m)). The wash cycle continues for the
length of time set on wash timer #1 (T1), adjustable from 0 to 600 seconds. At the end of wash cycle #1 the blue WASH
#1” pilot and the hot water solenoid valve #1 shut off and the blue “WASH #2” pilot and hot water solenoid valve #2
energize. The detergent and water mixture washes the second group of ventilators (up to 50 ft. (15m)). The wash cycle
continues for the length of time set on wash timer #2, adjustable from 0 to 600 seconds. At the end of wash cycle #2 the
blue “WASH #2” pilot and the hot water solenoid valve #2 shut off and the blue “WASH #3” pilot and the hot water
solenoid valve #3 energize. The detergent water mixture washes the third group of ventilators (also up to 50 ft. (15 m)).
At the end of wash cycle #3 the blue “WASH #3” pilot the hot water solenoid valve #3 and the detergent pump shut off.
The system remains idle until the next time the fan selector switch is rotated to “ON” position.
FOUR AND FIVE SEQUENCE WASH SYSTEMS
Four and five sequence wash control panels operate similarly
to the three-sequence wash. After the third wash cycle is
complete the system proceeds to the fourth and fifth wash
cycles.
Due to space limitations within the kitchen the four and five
sequence wash system also have remote solenoid valves.
The detergent pump and tank are still located in the wash
control panel. See wiring and piping diagrams in the back of
the manual for the four and five sequence wash systems.
MP40C & MP40H Water Wash Panel
Figure 9
H2
H3
WASH PILOT #3
WASH PILOT #2
HOT WATER SOLENOID #3
HOT WATER SOLENOID #2
B
B
I1
Q: 1 2 3 4 RUN
SMART RELAY
INTERNAL WIRING BY SPRING AIR
I1
SMART RELAY
Q: 1 2 3 4 RUN
H1
Set length
wash here.
and third
of second
B03=WASH3
B02=WASH2
Q1
Q2
I: 1 2 3 4 5 6
L
N
C
N
Set clock
L
B01=WASH1
B04=CLOCK
wash here.
and length
of first
Q1
Q2
Mo 09:00
I: 1 2 3 4 5 6
FAN SWITCH
OFF/AUTO/ON
ALL HOT WATER SOLENOID VALVES
ARE LOCATED REMOTE FROM PANEL
POWER SUPPLY TO THE AP20H/C PANEL
24 HOURS/DAY - 120V/1/60 - 15 AMPS
REMOTE WIRING BY TRADES
POWER TO THE EXHAUST FAN MOTOR STARTER
120V/1/60 - 2 AMPS MAXIMUM.
LV10 PANEL - 120V/1/60 - 2 AMPS MAXIMUM.
(OPTIONAL) POWER SUPPLY TO SUPPLY FAN
MOTOR STARTER - 120V/1/60 - 2 AMPS MAXIMUM
SHUTOFF DAMPER AND END SWITCH 120V/1/60
2 AMPS MAXIMUM.
POWER TO SHUNT TRIP TO DE-ACTIVATE ELECTRIC
COOKING EQUIPMENT IN THE EVENT OF A FIRE
120V/1/60 - 2 AMPS MAXIMUM. (SHUNT TRIP OR
POWER TO THE SPRING AIR SYSTEMS ENVIRO FILTER UNIT
(OPTIONAL) THREE (3) WIRES TO SUPPLY AIR MOTORIZED
RELAY SUPPLIED AND INSTALLED BY ELECTRICAL DIVISION)
DAMPER END SWITCH
REMOTE WIRING FOR ARRANGEMENT "F" & "T" TYPE FIRE DAMPER HOODS
ONLY. ARRANGEMENT "D" FIRE DAMPER HOODS REQUIRES NO REMOTE WIRING.
ESC
OK
Q3
Q4
I3
I2
I6
I4
I5
HOT WATER SOLENOID #1
WASH PILOT #1
WATER SOLENOID
OPTIONAL COLD
FAN PILOT
B
G
4
1
2
1
2
5
WHITE
RED
1
I6
I4
I3
I2
I5
ESC
OK
Q3
Q4
DETERGENT
PUMP
R5
FIRE TEST
PUMP TEST
8
10
9
R5
4
4
R5
4
4
10
9
4
8
4
9
1
1
2
3
5
4
4
3
1
NORMALLY OPEN
WET CHEMICAL CONTROL
TWO (2) WIRES TO THE
OR
ARRANGEMENT "F" FIRE DAMPERS:
TWO (2) WIRES TO EACH ENS ENCLOSURE LOCATED
AT EACH EXHAUST DUCT COLLAR ON EVERY HOOD
ARRANGEMENT "T" FIRE DAMPER:
AT EACH EXHAUST DUCT COLLAR ON EVERY HOOD
120V/1/60 - 1 AMPS. WIRE EACH ENS IN PARALLEL.
THREE (3) WIRES TO EACH SOE ENCLOSURE LOCATED
120V/1/60 - 3 AMPS - WIRE EACH SOE IN PARALLEL.
HEAD 120V/1/60 - 1A.
FENWALL DETECTOR
DAMPER SOLENOID
END SWITCH
OR
CURCUIT BREAKER
x x o
x
o
x
o
o
x