Spring Air Systems AP10C Скачать руководство пользователя страница 30

_____________________________________________________________________________________________ 

Spring Air Systems Water Wash Ventilator Maintenance Manual 11/01 

28 

 

 

AP20C & AP20H two sequence electrical wiring 

Figure 36 

 

AP30C & AP30H three sequence electrical wiring 

Figure 37 

 

I1

Q: 1 2 3 4  RUN

SMART RELAY

INTERNAL WIRING BY SPRING AIR

H2

H1

Set clock
and length

wash here.

B02=WASH2

B01=WASH1

B04=CLOCK

of first

Mo  09:00

Q1

Q2

I: 1 2 3 4 5 6

L

N

OFF/AUTO/ON

FAN SWITCH

REMOTE WIRING BY TRADES

120V/1/60 - 2 AMPS MAXIMUM.

24 HOURS/DAY - 120V/1/60 - 15 AMPS

POWER SUPPLY TO THE AP20H/C PANEL

2 AMPS MAXIMUM.

RELAY SUPPLIED AND INSTALLED BY ELECTRICAL DIVISION)

120V/1/60 - 2 AMPS MAXIMUM.  (SHUNT TRIP OR

COOKING EQUIPMENT IN THE EVENT OF A FIRE

POWER TO SHUNT TRIP TO DE-ACTIVATE ELECTRIC

SHUTOFF DAMPER AND END SWITCH 120V/1/60 

(OPTIONAL) THREE (3) WIRES TO SUPPLY AIR MOTORIZED

MOTOR STARTER - 120V/1/60 - 2 AMPS MAXIMUM

(OPTIONAL) POWER SUPPLY TO SUPPLY FAN

LV10 PANEL - 120V/1/60 - 2 AMPS MAXIMUM.

POWER TO THE SPRING AIR SYSTEMS ENVIRO FILTER UNIT 

POWER TO THE EXHAUST FAN MOTOR STARTER

DAMPER END SWITCH

REMOTE WIRING FOR ARRANGEMENT "F" & "T" TYPE FIRE DAMPER HOODS

ONLY.  ARRANGEMENT "D" FIRE DAMPER HOODS REQUIRES NO REMOTE WIRING.

FAN PILOT

C

WATER SOLENOID

G

OPTIONAL COLD

WASH PILOT #1

HOT WATER SOLENOID #1

HOT WATER SOLENOID #2

WASH PILOT #2

B

B

DETERGENT
PUMP

2

4

2

1

1

WHITE

RED

5

1

R5

ESC

Q3

Q4

OK

I2

I3

I6

I4

I5

R5

R5

CURCUIT BREAKER

FIRE TEST

PUMP TEST

3

5

4

8

9

10

4

3

4

4
8
9

4

10

4

4
9

1

1

2

4

1

OR

ARRANGEMENT "T" FIRE DAMPER:

ARRANGEMENT "F" FIRE DAMPERS:

TWO (2) WIRES TO THE
WET CHEMICAL CONTROL
HEAD  120V/1/60 - 1A.

120V/1/60 - 3 AMPS - WIRE EACH SOE IN PARALLEL.

THREE (3) WIRES TO EACH SOE ENCLOSURE LOCATED

120V/1/60 - 1 AMPS.  WIRE EACH ENS IN PARALLEL.

AT EACH EXHAUST DUCT COLLAR ON EVERY HOOD

AT EACH EXHAUST DUCT COLLAR ON EVERY HOOD

TWO (2) WIRES TO EACH ENS ENCLOSURE LOCATED

FENWALL DETECTOR

DAMPER SOLENOID

END SWITCH

NORMALLY OPEN

OR

x x o

x

o

x

o

o

x

H2

H3

WASH PILOT #3

WASH PILOT #2

HOT WATER SOLENOID #3

HOT WATER SOLENOID #2

B

B

I1

Q: 1 2 3 4  RUN

SMART RELAY

INTERNAL WIRING BY SPRING AIR

I1

SMART RELAY

Q: 1 2 3 4  RUN

H1

Set length

wash here.

and third

of second

B03=WASH3

B02=WASH2

Q1

Q2

I: 1 2 3 4 5 6

L

N

C

N

Set clock

L

B01=WASH1

B04=CLOCK

wash here.

and length
of first

Q1

Q2

Mo  09:00

I: 1 2 3 4 5 6

FAN SWITCH

OFF/AUTO/ON

ALL HOT WATER SOLENOID VALVES
ARE LOCATED REMOTE FROM PANEL

POWER SUPPLY TO THE AP20H/C PANEL
24 HOURS/DAY - 120V/1/60 - 15 AMPS

REMOTE WIRING BY TRADES

POWER TO THE EXHAUST FAN MOTOR STARTER
120V/1/60 - 2 AMPS MAXIMUM.

LV10 PANEL - 120V/1/60 - 2 AMPS MAXIMUM.

(OPTIONAL) POWER SUPPLY TO SUPPLY FAN
MOTOR STARTER - 120V/1/60 - 2 AMPS MAXIMUM

SHUTOFF DAMPER AND END SWITCH 120V/1/60 
2 AMPS MAXIMUM.

POWER TO SHUNT TRIP TO DE-ACTIVATE ELECTRIC
COOKING EQUIPMENT IN THE EVENT OF A FIRE
120V/1/60 - 2 AMPS MAXIMUM.  (SHUNT TRIP OR

POWER TO THE SPRING AIR SYSTEMS ENVIRO FILTER UNIT 

(OPTIONAL) THREE (3) WIRES TO SUPPLY AIR MOTORIZED

RELAY SUPPLIED AND INSTALLED BY ELECTRICAL DIVISION)

DAMPER END SWITCH

REMOTE WIRING FOR ARRANGEMENT "F" & "T" TYPE FIRE DAMPER HOODS

ONLY.  ARRANGEMENT "D" FIRE DAMPER HOODS REQUIRES NO REMOTE WIRING.

ESC

OK

Q3

Q4

I3

I2

I6

I4

I5

HOT WATER SOLENOID #1

WASH PILOT #1

WATER SOLENOID

OPTIONAL COLD

FAN PILOT

B

G

4

1

2

1

2

5

WHITE

RED

1

I6

I4

I3

I2

I5

ESC

OK

Q3

Q4

DETERGENT

PUMP

R5

FIRE TEST

PUMP TEST

8

10

9

R5

4

4

R5

4

4

10

9

4

8

4

9

1

1

2

3

5

4

4

3

1

NORMALLY OPEN

WET CHEMICAL CONTROL

TWO (2) WIRES TO THE

OR

ARRANGEMENT "F" FIRE DAMPERS:
TWO (2) WIRES TO EACH ENS ENCLOSURE LOCATED
AT EACH EXHAUST DUCT COLLAR ON EVERY HOOD

ARRANGEMENT "T" FIRE DAMPER:

AT EACH EXHAUST DUCT COLLAR ON EVERY HOOD

120V/1/60 - 1 AMPS.  WIRE EACH ENS IN PARALLEL.

THREE (3) WIRES TO EACH SOE ENCLOSURE LOCATED

120V/1/60 - 3 AMPS - WIRE EACH SOE IN PARALLEL.

HEAD  120V/1/60 - 1A.

FENWALL DETECTOR

DAMPER SOLENOID

END SWITCH

OR

CURCUIT BREAKER

x x o

x

o

x

o

o

x

Содержание AP10C

Страница 1: ...VENTILATOR MAINTENANCE MANUAL ___________________________ Spring Air Systems Inc Oakville Ontario Phone 905 338 2999 Fax 905 338 0179...

Страница 2: ...d Line Fire Suppression Arrangement T 21 Second Line Fire Suppression Arrangement F 22 Variflow Baffles 23 SB10H One Sequence Wash Plumbing Schematic 24 SBA10C One Sequence Wash Plumbing Schematic 25...

Страница 3: ...l with all the edges ground and polished All ventilators are manufactured to stringent quality standards and are guaranteed to enhance the appearance of any commercial kitchen Model HT B Water wash Ve...

Страница 4: ...water wash D Dry Grease Extractor T Thermostatic Fire Damper F Fusible link spring loaded fire damper D Fusible link dead weight fire damper S Shelf type hood B Box type hood BS Box shelf type hood D...

Страница 5: ...rgized through terminals 4 9 When a motorized damper with end switch is not used in the installation the field electrician must jumper terminals 8 9 in the water wash panel to provide 120V 1 60 power...

Страница 6: ...continues for the period of time set on the wash timer adjustable from 0 to 600 seconds At the end of the wash cycle the blue WASH pilot the detergent pump and the hot water solenoid valve shut off Th...

Страница 7: ...2 4 Hot water solenoid valve 2 H3 4 Hot water solenoid valve 3 OPTIONAL COLD WATER SOLENOID HOT WATER SOLENOID H C FAN PILOT WASH PILOT B PUMP DETERGENT G SMART RELAY Q 1 2 3 4 RUN INTERNAL WIRING BY...

Страница 8: ...systems MP40C MP40H Water Wash Panel Figure 9 H2 H3 WASH PILOT 3 WASH PILOT 2 HOT WATER SOLENOID 3 HOT WATER SOLENOID 2 B B I1 Q 1 2 3 4 RUN SMART RELAY INTERNAL WIRING BY SPRING AIR I1 SMART RELAY Q...

Страница 9: ...Breaker Figure 10 CLEANING THE EXTERIOR Normal soil can be removed with a mild detergent water mixture applied to a cloth To remove baked on grease apply a cleanser to a damp cloth or sponge and rub...

Страница 10: ...WASH SYSTEMS SBA10H SBA10C AP10H AP10C AP20H AP20C AP30H AP30C AP40H AP40C AP50H AP50C The automatic wash control panels are equipped with a solid state microprocessor The fan selector switch is repla...

Страница 11: ...ng until the correct hour appears 4 To change the time press once The hour will be highlighted Press 1 Press these two buttons together Su 11 25 Q 1 2 3 4 I 1 2 3 4 5 6 Su 11 25 Set Clock 11 11 01 MM...

Страница 12: ...bove settings press 4 The clock has been factory set to turn the fan on at 6 00 a m and off to the minute the fan stop in the evening Press to change the minutes to change the hour you want the fan to...

Страница 13: ...the hour that the fan will stop in the evening Press to change the hour you want the fan to stop each evening Press to move to the minute the fan stop in the evening Press to change the minutes to the...

Страница 14: ...minutes 4 The clock has been factory set to turn the fan on at 6 00 a m and off at 23 00 hours or 11 00 p m When the fan shuts off the wash activates To change these times see section Programming the...

Страница 15: ...120V 1 60 2 AMPS MAXIMUM OPTIONAL POWER SUPPLY TO SUPPLY FAN LV10 PANEL 120V 1 60 2 AMPS MAXIMUM POWER TO THE SPRING AIR SYSTEMS ENVIRO FILTER UNIT POWER TO THE EXHAUST FAN MOTOR STARTER DAMPER END SW...

Страница 16: ...secondary coverage as the exhaust air enters the secondary grease extraction chamber The exhaust air continues into the secondary extraction chamber which contains an additional baffle F Residual gre...

Страница 17: ...TYPE RECOMMENDED COOKING USE Type C Medium heavy and heavy duty Mesquites live charcoal Gas charbroilers heavy frying Type H Medium and medium heavy duty Gas charbroilers Fryers Ranges Griddles Most c...

Страница 18: ...ater wash time because of the continuous cold water spray During fan and cooking operation the spray continuously carries grease dirt and lint down the drain which reduces the daily grease build up Th...

Страница 19: ...nstallation Remote wiring and plumbing are shown for an exhaust fan wet chemical systems a Spring Air Systems water wash hood and a SB10H water wash panel In addition to the wiring indicated below pow...

Страница 20: ...1 0 3353 7 3 8 9 40 5 50 0 11 5 3505 7 9 9 7 44 2 54 0 12 0 3658 7 9 9 7 44 2 54 0 12 5 3810 8 5 10 4 47 4 57 9 13 0 3962 8 5 10 4 47 4 57 9 13 5 4115 9 2 11 3 51 4 63 0 14 0 4207 9 2 11 3 51 4 63 0 1...

Страница 21: ...7 1 14 5 4420 17 6 21 5 66 6 81 3 15 0 4772 17 6 21 5 66 6 81 3 Chart No 3 Cold Water Required Model DB Ventilator Length Cold Water Flow USGPM Cold Water Flow l s Ventilator Length Cold Water Flow US...

Страница 22: ...fan motor starter is shut off NOTE The exhaust fan remains on after a primary surface fire suppression system has activated Arrangement D Fusible Link Activated Dead Weight The arrangement D hood and...

Страница 23: ...e wash control panel through terminal 2 Within the water wash control panel the fire relay R5 is energized activating the water wash control panel hood and damper assembly 1 The exhaust fan is shut of...

Страница 24: ...STITUTE FOR THE SURFACE FIRE SUPPRESSION SYSTEM WET CHEMICAL SPRINKLER ETC A SURFACE FIRE PROTECTION MUST BE INSTALLED IN ACCORDANCE WITH APPLICABLE CODES Arrangement F Fusible Link Activated Spring L...

Страница 25: ...ARIFLOW baffles located above a charbroiler are opened to the maximum 450 CFM ft position and the VARIFLOW baffles located above ovens or steamers are closed to the minimum 90 CFM ft position This var...

Страница 26: ...n at about 300 CFM ft The baffles are connected to the Primary baffle on studs fastened by wing nuts There a total of five 5 adjustment positions on each baffle After the water wash hood is installed...

Страница 27: ..._____________________ Spring Air Systems Water Wash Ventilator Maintenance Manual 11 01 25 SBA10C hot water wash cold water spray plumbing Figure 29 MP20C two sequence hot water wash cold water spray...

Страница 28: ..._________________________________________________________ Spring Air Systems Water Wash Ventilator Maintenance Manual 11 01 26 AP30C three sequence hot water wash plumbing Figure 32 MP30H three sequen...

Страница 29: ...T WASH PILOT B PUMP WATER SOLENOID OPTIONAL COLD FAN PILOT G 1 5 INTERNAL WIRING BY SPRING AIR FIRE TEST PUMP TEST I3 FAN SWITCH Q 1 2 3 4 RUN Mo 09 00 I 1 2 3 4 5 6 SMART RELAY Q1 Q2 N L I1 I2 OFF AU...

Страница 30: ...WO 2 WIRES TO EACH ENS ENCLOSURE LOCATED FENWALL DETECTOR DAMPER SOLENOID END SWITCH NORMALLY OPEN OR x x o x o x o o x H2 H3 WASH PILOT 3 WASH PILOT 2 HOT WATER SOLENOID 3 HOT WATER SOLENOID 2 B B I1...

Страница 31: ...check the VORTEX BAFFLE and grease trough for any debris Check that the drain is free and clear SIX MONTHS 1 Clean all line strainers located in the control panel hot water and cold water 2 Check exha...

Страница 32: ...he throat inlet slot of the ventilator Velometer should not exceed three inches in diameter Measuring Exhaust Air Figure 38 PITOT TUBE OR ANEMOMETER Hold the instrument perpendicular to the VORTEX BAF...

Страница 33: ...er drawings 6 Check that all electrical connections are tight and secure 7 Check exhaust duct connections 8 Check that fire damper is open 9 Open ventilator access door and check drain and grease trou...

Страница 34: ...amper only iii Faulty end switch in Fire Damper End Switch Enclosure ENS Arrangement F dampers only iv Fire relay R6 is faulty AP10 SBA10 type only B Blue WASH ON pilot is off i Hot water solenoid val...

Страница 35: ...Air Design CFM Ventilator mounting Height from finished floor to front of hood Make Up Air Systems Good Fair Poor None Hood Item Model Length Width No of Baffles Baffle Size Design CFM Baffle No Left...

Страница 36: ...s in remote hot water piping 14 Water Pressure psi 15 Water temperature F 16 Length of wash minutes 17 Water leaks in ventilator 18 Drain runs clear 19 At the end of the wash 20 Hot water solenoid off...

Страница 37: ...Using your fingers unscrew the diaphragm counter clockwise 5 When replacing old diaphragm with new check to make sure the size of the spacers is the same located under the nut on the diaphragm 6 When...

Страница 38: ...Set Param Set Clock Mo 09 00 Su 09 00 Q 1 2 3 4 or OK 2 Press I 1 2 3 4 5 6 to return to the operating screen until correct year appears Press to move to day until correct day appear Press to until co...

Отзывы: