Set the date and time
1.
Move the wheels of the time indicator (HH:MM:SS)
to the correct time in hours (HH), minutes (MM),
and seconds (SS).
2.
Move the wheels of the date indicator (DD:MM:YY)
to the correct date in day (DD), month (MM), and
year (YY).
3.
Select the next page button ( > ).
4.
Open the valves. Refer to § 5.4.1.
5.
Deaerate the pump. Refer to § 5.4.1.
Set the pressure levels
1.
Drag the label of the maximum pressure (A) to the
desired maximum pressure.
2.
For units of -R and -B versions:
Drag the label of
the operating pressure (B) to the desired operating
pressure.
3.
For units of -R and -B versions:
Drag the label of
the refill pressure (C) to the desired refill pressure.
4.
Select the confirm button (
).
Start the degassing process
1.
Select the degassing button. The button indicator
light comes on.
2.
Select the home button to go to the home screen.
5.4.3
Check operation
1.
Check the indication of the pressure gauge (B). This
should alternately display overpressure and
underpressure.
2.
Close the valve (A) behind the pressure gauge.
3.
Put back the cover (C) on the unit and fasten it with
the two bolts (D).
6
OPERATION
6.1
HMI (user interface) description
This section shows an overview of the content on the
display.
6.1.1
Screen layout
A
Date and time indicator
B
Operating mode indicator
NOTE
The minimum operating pressure (D) cannot
be changed.
NOTE
In case the unit is not filled to at least the
minimum operating pressure (2.1 bar for
S6), the degassing process will not start and
you will get a error message. Refer to § 7.5.
D
B
C
A
NOTE
The SmartSwitch will automatically turn
off the unit when the concentration of
dissolved gases has reached the minimum
level.
D
C
D
B
A
B
C
A
D
E
Standby
System pressure: xxx bar