5.1
Installation conditions
Install the unit on a frost-free, well-ventilated place.
Install the unit in accordance with the local
guidelines and rules.
Connect the unit to a 230 V / 50 - 60 Hz supply.
Install the unit as bypass on the main line of the
installation.
Preferably install the unit at the point in the
installation with the lowest temperature. Here the
most dissolved gases are found in the fluid.
In case of a heavily contaminated system fluid, a
dirt separator is to be installed in the main return
line of the installation.
Make sure that the expansion system has the
proper dimensions. The water displacement in the
unit can cause pressure variations in the
installation. Take into account an extra net
expansion volume of at least 2 litres. Make sure the
expansion system connection is properly sized (at
least ¾"/22mm diameter).
Make sure that the operating panel is always easily
accessible.
Make sure that you maintain at least the distance as
indicated for service and repair.