Spirax Sarco SX75 Series Скачать руководство пользователя страница 6

4

Lit with output Y1 “ON”

Not lit with continuous or dual action

discontinuous output

Lit

with

output

Lit with output Y2 “ON”

Lit with output Y3 “ON”

Lit in Manual operation

Lit when the Remote Set point is operating

(if off, the operating Set point is the Local one)

Lit when Auto-Tune function is activated

Permanently lit when the serial

communication is enabled to write.

Flashes with signal in transit

Loop -

Break -

Alarm

With output Y3 active and configured as

Loop Break Alarm, the front displays X and

W will flash (see p. 15)

3

2

1

Output Y1 (red)

Output Y1 (red)

Output Y1F (red)

Output Y2 (red)

Output Y3 (red)

Manual (green)

Remote (green)

Auto-Tune (green)

Serial comm. (green)

LEDS FOR OUTPUT STATE

Lit

with

output

MAN

REM

AT

SCI

Y1 "ON" (increasing valve motor drive position)

Y1 (heat) "ON" - dual action

Y1 "ON" (decreasing valve motor drive position)

Y1 (cool) "ON" - dual action

LEDS FOR OPERATING STATE

275.8

275.8

50

4

2. FUNCTION OF KEYS AND DISPLAYS

Содержание SX75 Series

Страница 1: ...3231350 3 Issue 3 Printed in the UK Copyright 2006 SX75 Series Process Controller Installation and Maintenance Instructions...

Страница 2: ...WORD PROTECTION page 15 6 PROGRAMMING INSTUCTIONS FUNCTIONS MENU CONFIGURATION SETTING OF PARAMETERS see enclosed leaflet 7 OPERATING INSTUCTIONS second leaflet FUNCTIONS MENU CHANGING NUMERIC VALUES...

Страница 3: ...controller is designed as an installation category II product and is reliant on the building installation for over current protection and primary isolation Wiring should be carried out in accordance...

Страница 4: ...product or its wiring is located near a radio transmitter Excessive electrical noise occurs on the mains supply Cellular telephones and mobile radios may cause interference if used within approximate...

Страница 5: ...of measure X is expressed in engineering units If value over range If value under range In parameters displays parameter values In configuration displays the values of EFGH configuration code see encl...

Страница 6: ...to write Flashes with signal in transit Loop Break Alarm With output Y3 active and configured as Loop Break Alarm the front displays X and W will flash see p 15 3 2 1 Output Y1 red Output Y1 red Outp...

Страница 7: ...ing Enter or Scroll of values and modes of operation Change from Automatic to Manual operation and vice versa Set Point Digit selection Increment digit Functions Enter Auto Man KEYS 1 Local 4 storable...

Страница 8: ...jection W F A M AMBIENT Temperature 0 50 C Humidity 30 85uR Install away from heat sources corrosive gases dusty environments Do NOT force cross screwdriver HR mV V A kW psi Bar F MPa l m m3 h Nm3 h C...

Страница 9: ...e plate to free the location pin 2 Depress the plate to engage the pin 1 Rotate upwards With eyelet terminals 6 9 max With tinned wire 6 7 With fork terminals 6 9 max Cable section wires N 0 25 2 5 AW...

Страница 10: ...20 11 1 Single out supply line from power line Keep away from electromagnetic contactors and powerful motors Channel for low level signal conductors Power supply and output channels A B C D E A B C D...

Страница 11: ...or wire A B B 7 9 10 B For RTD Pt100 C Continuous mA Volt Input mA Volt Auxiliary supply for transmitter 6 7 9 Rj X i 4 20 mA 6 7 9 Rj Transmitter 24 Vdc For 2 wire transmitter For 3 or 4 wire transmi...

Страница 12: ...C2 H C3 External contacts Closing of contacts C1 C2 C3 for two seconds permits the selection AUTO or MAN Local or Remote Set point and recalling the 4 memorized Set points 4 Logic inputs From 100 to 1...

Страница 13: ...will protect the controller from switching the actuators high current loads avoid introducing high current loops within the proximity of the controller and provide an easily replaceable switching ele...

Страница 14: ...act rating 5A 250Vac for resistive loads transition 2 x 10 coeff 5 min at 5A 250Vac 6 Main output Y1 Y1 Y1 B single in current 450 W max 19 20 C single in voltage 19 20 Load Load D single logic Y1 19...

Страница 15: ...limit 0 100 Y1F limit 0 100 0 100 100 0 Cool Heat Cool 100 Y1F output cool Y1C output heat Output feature of dual action controllers NA Dead band 6 Main output Y1 continued Terminals 16 17 Y1 s Heat...

Страница 16: ...oint W of output Y1F Cool Passing from 4 20mA standard to 0 10Vdc by moving a JUMPER inside the controller 4 20 mA 0 10 Vdc Y4 Retransmission output Y1F option TX RX 2 3 4 1 Transmission Reception Int...

Страница 17: ...swords have to be entered 5 2 Access to programming group 3 parameters password 1111 1111 3333 1111 Enter password of access to configuration see enclosed leaflet OK Return to normal function YES NO I...

Страница 18: ...e of these set values is recalled the small auxil iary display on the front of the instru ment shows the set number recalled sl u Rate of change for increase of the main set point SP Any new value of...

Страница 19: ...escription Customer set Values C_F C or F 0 Group1 Set point parameter settings Parameter Description Default Customer set Value Values S P 1 Set point 1 10 40 S P 2 Set point 2 20 60 S P 3 Set point...

Страница 20: ...een 0 to 300 steps This value is with reference to set point W Active high Active low Event set point is variable within the input signal scale range Active high Active low Event set point is variable...

Страница 21: ...input or output signals will cause the output Y3 to be energized after a few minutes and front display X and W will flash The alarm state will stop when the fault is corrected or if a key is pressed...

Страница 22: ...al Sp to Remote Sp __ ON C2 C3 C1 IL2 IL3 IL1 Operating mode options COM IL1 IL2 IL3 H C1 21 22 23 24 H C2 H C3 External contacts Note 1 Is possible to fix the selected Set point holding closed the re...

Страница 23: ...radient slope 0 1 100 0 digit min Higher and lower limit from beginning to end of scale Local Remote Set point In current 4 20mA Ri30 Not isolated accuracy 0 1 at 25 C In voltage 0 10Vdc Ri 330k Contr...

Страница 24: ...4 20mA 450W max 10Vdc max galvanically isolated Voltage 0 10Vdc 500W min 20mA max Serial commnication SX75 only Interface 20mA C L passive and galvanically isolated see manual MIU CS E or RS485 port P...