10. TECHNICAL DATA
Accuracy
(a25
°
C amb.)
0.2%
±
1 digit (for input with RTD Pt100 and thermocouples)
0.1%
±
1 digit (for input in current and voltage)
Input "X"
(configurable)
RTD Pt100
Pt100
Ω
@ 0
°
C, (IEC 751)
With
configurable
scale field
Thermocouples
J-K-S-R (IEC 584), L (DIN 43710)
Continuous current
4..20mA, 0..20mA, Ri 30
Ω
Continuous voltage
0..1Vdc, 0..10Vdc, Ri 10K
Ω
Auxiliary
inputs
3 of logic type (control of operating and Set point states)
Set point
1 Local + 4 storable
2 ramps for ascent and
descent gradient slope
0.1´100.0 digit/min.
Higher and lower limit
from beginning to end of scale
Local/Remote
Set point
In current
4..20mA, Ri30
Ω
Not isolated
accuracy:
0.1% at 25
°
C.
In voltage
0..10Vdc, Ri 330k
Ω
Control
actions
Algorithm
On - Off, PID, FUZZY, PID with I and D
excludable actions.
Proportional band (P)
0,5..999.9%
Integral action time (I)
0.1..100min., excluded
Derivative action time (D)
0.01..10min., excluded
Cycle time
1..200 sec. (for discontinuous control)
Hysteresis
0.1..10% (for on-off control)
Dead zone
±
0´5,0% for dual action (heat-cool)
Auto - Tune
For automatic parameter adjustment (One shot)
Auto/Man
Station
With bumpless action, AUTO/MAN transfer via keyboard, logic input and serial
communication.