10.8 Programming parameters / default settings
The default settings in this table are used in the 'quick start' guide - See Section 6.3.1.
InS - Input Select
Ranges
1-6 or 4.20
Default
1-6
Units
Vdc or mA
InF - Input Filter
Ranges
2, 8 or 16
Default
2
Units
Seconds
InA - Input Alarm (Out-of-range)
Ranges
OFF or ON
Default
OFF
AS1 - Alarm 1 select
Ranges
Hi or Lo
Default
Hi
AP1 - Alarm 1 percentage (of gauge glass)
Ranges
5 – 100 (high alarm) or 0 – 95 (low alarm)
Default
85 (high alarm) or 20 (low alarm)
Resolution
1
Units
%
AS2 - Alarm 2 select
Ranges
Hi or Lo
Default
Lo
AP2 - Alarm 2 percentage (of gauge glass)
Ranges
5 – 100 (high alarm) or 0 – 95 (low alarm)
Default
85 (high alarm) or 20 (low alarm)
Resolution
1
Units
%