2000 Series
For Systems with Ranges starting at
Cool System to
Suggested Cooling Means
90 to 110°F
32 to 43°C
50°F / 10°C or lower
Tap water mixed with ice as needed
65 to 85°F
18 to 29°C
32°F / 0°C or lower
Crushed ice mixed with water
45 to 60°F
7 to 16°C
10°F / -12°C or lower
Crushed ice mixed with plenty of salt
-15 to 40°F
-26 to 4°C
-35°F / -37°C or lower
Alcohol and “dry ice”
Table 3
. Replacement Thermal Systems
REGULATOR
SETTING
RANGE, °F
45 to 115
45 to 145
65 to 140
65 to 170
240 to 310
240 to 340
0
1
45
50
65
70
236
240
2
58
70
80
91
250
267
3
72
87
92
108
265
281
4
81
102
103
125
275
296
5
92
114
114
137
285
308
6
101
124
124
147
295
318
7
108
135
131
158
303
329
8
115
143
138
167
310
337
9
122
152
145
177
317
347
10
129
158
157
183
322
353
REGULATOR
SETTING
RANGE, °C
7.2 to 46
7.2 to 63
18 to 60
18 to 77
116 to 154
116 to 171
0
1
7
10
18
21
113
116
2
14
21
27
33
121
131
3
22
31
33
42
129
138
4
27
39
39
52
135
147
5
33
46
46
58
141
153
6
38
51
51
64
146
159
7
42
57
55
70
151
165
8
46
62
59
75
154
169
9
50
67
63
81
158
175
10
54
70
69
84
161
178
- Control points at these settings are slightly below the low end of the regulator range.
Table 4
. Approximate Temperature Equivalents for Various Scale Settings
BULB RANGES
MAXIMUM OVER TEMPERATURE
Short
Long
°F
°C
°F
°C
°F
°C
45 to 115
10 to 45
45 to 145
10 to 60
450
230
450
230
65 to 140
20 to 60
65 to 170
20 to 75
450
230
120 to 200
50 to 90
120 to 230
50/ to 110
300
150
240 to 310
115 to 155
240 to 340
115 to 170
350
175
280 to 375
138 to 191
280 to 415
138 to 213
450
230
Table 5
. 2000 Series Bulb Ranges