6
7
SPEL Stormwater Installation & Operation Manual |
SPEL Filter
Sizes
SPEL Stormwater manufactures two height cartridges for varying site constraints as shown below. Each cartridge
is designed to treat stormwater at a flow rate of 1.47 Litres per second and 2.83 Litres per second for the half-
height cartridge (model No. SF.15-EMC-M) and full-height cartridge (model No. SF.30-EMC-M) respectively.
Full Height SF.30-EMC -M
Half height SF.15–EMC-M
SPELFilter total height
874mm
560mm
SPELFilter Diameter
726mm
726mm
Minimum Head required
850mm
450mm
Treatment flow rate
2.83 L/s
1.47 L/s
Height of inlet ports above
vault floor
240mm
240mm
Filtered water collection
pipe diameter
50mm
50mm
SPELFilter Full Height- SF.30-EMC-M
SPELFilter Half Height - SF.15-EMC-M