Micro800™ 4 Ch Universal Analog Input Module
15
Publication 0100189-04 Rev. C
Environmental Tests
Industry Standards
Test Level Limits
Radiated Emissions
CSIPR 11; Group 1, Class A
Rockwell Document QTP#X0327
(Enclosure) Class A, 30 MHz
– 1
GHz
Conducted Emissions
IEC 61000-6-4:2007
Rockwell Document QTP#X0327
Group 1, Class A (AC Mains), 150
kHz
– 30 MHz
ESD immunity
(Performance Criteria B)
IEC 61000-4-2
Rockwell Document QTP#X0327
6 kV Indirect (Coupling Plate)
6 kV Contact Discharge (to points
of initial contact)
8 kV Air Discharge (to points of
initial contact)
Radiated RF immunity
(Performance Criteria A)
IEC 61000-4-3: Level 3
Rockwell Document QTP#X0327
10 V/M with 1 kHz sine-wave 80%
AM from 80…2000 MHz
10 V/M with 200 Hz sine-wave
50% Pulse 100% AM @900 MHz
10 V/M with 200 Hz sine-wave
50% Pulse 100% AM @1890 MHz
1 V/M with 1 kHz sine-wave 80%
AM from
2000…2700 MHz
(3 V/M goal)
EFT/B immunity
(Performance Criteria B)
IEC 61000-4-4*
Rockwell Document QTP#X0327
Signal Ports:
± 3 kV @ 5 kHz for 5 minutes,
Criteria B (Marine?)
± 2 kV @ 5 kHz for 5 minutes,
Criteria A (Marine?)
± 2 kV @ 5 kHz for 5 minutes,
Criteria B (standard)
Power Ports:
± 2 kV @ 5 kHz for 5 minutes,
Criteria A (Marine?)
± 2 kV @ 5 kHz for 5 minutes,
Criteria B (standard)
Surge transient immunity
(Performance Criteria B)
IEC 61000-4-5
Rockwell Document QTP#X0327
Signal Ports:
± 2 kV line-
earth {CM}@ 2Ω on
shielded ports
Power Ports
± 2 kV CM @ 12
Ω
± 1 kV DM @ 2
Ω
Conducted RF immunity
(Performance Criteria A)
IEC 61000-4-6
Rockwell Document QTP#X0327
10 V rms with 1 kHz sine wave
80%
AM from 150 kHz…80 MHz
on signal and power ports