A-2
Appendix A: Module Specifications
User’s Manual Pub. 0300247-01 Rev. D
Specification
Value
Recommended Cable
Belden™ 8761 (shielded)
Specification
Value
Vendor I.D.
58
Product Type
10
Product Code
22
Agency Certification
C-UL listed (under CSA C22.2 No. 142)
UL 508 listed
CE compliant for all applicable directives
Hazardous Environment
Class
Class I, Division 2, Hazardous Location, Groups A, B, C,
D
(ISA 12.12.01, C-UL under CSA C22.2 No. 213)
Operating Temperature Code T4a
Radiated and
Conducted Emissions
EN61131-2
Electrical /EMC:
The module has passed testing at the following levels:
ESD Immunity
(IEC61000-4-2)
4 kV contact, 8 kV air, 4 kV indirect
Radiated Immunity
(IEC61000-4-3)
10 V/m, 80 to 1000 MHz, 80% amplitude modulation,
+900 MHz keyed
carrier
Fast Transient Burst
(IEC61000-4-4)
2 kV, 5 kHz
Surge Immunity
(IEC61000-4-5)
1 kV galvanic gun
Conducted Immunity
(IEC61000-4-6)
10 V, 0.15 to 80 MHz
6
6
Conducted Immunity frequency range may be 150 kHz to 30 MHz if the Radiated Immunity frequency
range is 30 MHz to 2700 MHz.
Содержание 1762sc-IF4OF4
Страница 1: ......
Страница 6: ...vi MicroLogix 1200 Analog Combo Module 4Ch IN 4Ch Out User s Manual Pub 0300247 01 Rev D...
Страница 12: ...1 6 Chapter 1 Module Overview User s Manual Pub 0300247 01 Rev D See the block diagram below ASIC...
Страница 34: ...3 12 Chapter 3 Configuring the 1762sc IF4OF4 for RSLogix 500 User s Manual Pub 0300247 01 Rev D...
Страница 41: ...Appendix A Module Specifications A 7 User s Manual Pub 0300247 01 Rev D...
Страница 42: ...A 8 Appendix A Module Specifications User s Manual Pub 0300247 01 Rev D...
Страница 44: ...User s Manual Pub 0300247 01 Rev D...
Страница 45: ...User s Manual Pub 0300247 01 Rev D...