Chapter 2: Installation and Wiring
User’s Manual Pub. 0300247-01 Rev. D
Table 2-1
Controller
Max 5 V
Bus Current
Max 24 V
Bus Current
Max # of IF4OF4 Modules
ML1100
800
700
4
ML1200 (24 pt.) 400
350
3
ML1200 (40 pt.) 600
500
3
ML1400 (All)
1500
1500
7
Section 2.3
General
Considerations
1762 I/O is suitable for use in an industrial environment when installed in
accordance with these instructions. Specifically, this equipment is intended for
use in clean, dry environments Pollution degree 2
1
and to circuits not exceeding
Over Voltage Category II
2
(IEC 60664-1)
3
.
2.3.1
Hazardous Location Considerations
This equipment is suitable for use in Class I, Division 2, Groups A, B, C, D or
non-hazardous locations only. The following WARNING statement applies to
use in hazardous locations.
WARNING
EXPLOSION HAZARD
Substitution of components may impair suitability for Class I,
Division 2. Touch a grounded object to discharge static potential.
Do not replace components or disconnect equipment unless power
has been switched off or the area is known to be non-hazardous.
Touch a grounded object to discharge static potential.
This product must be installed in an enclosure. Touch a grounded
object to discharge static potential.
All wiring must comply with N.E.C. article 501-4(b). Touch a
grounded object to discharge static potential.
1
Pollution Degree 2 is an environment where, normally, only non-conductive pollution occurs except that
occasionally a temporary conductivity caused by condensation shall be expected.
2
Over Voltage Category II is the load level section of the electrical distribution system. At this level,
transient voltages are controlled, and do not exceed the impulse voltage capability of the product’s
insulation.
3
Pollution Degree 2 and Over Voltage Category II are International Electrotechnical Commission (IEC)
designations.
Содержание 1762sc-IF4OF4
Страница 1: ......
Страница 6: ...vi MicroLogix 1200 Analog Combo Module 4Ch IN 4Ch Out User s Manual Pub 0300247 01 Rev D...
Страница 12: ...1 6 Chapter 1 Module Overview User s Manual Pub 0300247 01 Rev D See the block diagram below ASIC...
Страница 34: ...3 12 Chapter 3 Configuring the 1762sc IF4OF4 for RSLogix 500 User s Manual Pub 0300247 01 Rev D...
Страница 41: ...Appendix A Module Specifications A 7 User s Manual Pub 0300247 01 Rev D...
Страница 42: ...A 8 Appendix A Module Specifications User s Manual Pub 0300247 01 Rev D...
Страница 44: ...User s Manual Pub 0300247 01 Rev D...
Страница 45: ...User s Manual Pub 0300247 01 Rev D...