User’s Manual Pub. 0300247-01 Rev. D 

Appendix A 
Module Specifications 

 

General Specifications 

Specification  

Value 

Dimensions 

90 mm (height) × 87 mm (depth) 40 mm (width) 
Height including mounting tabs is 110 mm 
3.54 in. (height) × 3.43 in. (depth) × 1.58 in. (width) 
Height including mounting tabs is 4.33 in. 

Approximate Shipping Weight (with 
carton) 

281 g (0.619 lbs.) 

Storage Temperature 

-40 °C to +85 °C (-40 °F to +185 °F) 

Operating Temperature 

-20 °C to +60 °C (-4 °F to +140 °F) 

Operating Humidity 

5% to 95% non-condensing 

Operating Altitude 

2000 meters (6561 feet) 

Vibration 

Operating: 10 to 500 Hz, 5 G, 0.030 in. max. peak-to-peak 

Shock 

Operating: 30 G 

Bus Current Draw (max.) 

30 mA at 5 VDC Max 
3.4 W Max (140 mA max at 24 V) 

Heat Dissipation 

3.0 W Total Max 

Resolution 

16 bits (Integer Format) 

Channel Update Time 

Filter Setting 

Conversion 
Time 

Module Update time

5

 

470 Hz 

20 ms 

= Conversion time * 
(1+ number of 
enabled channels) 

62 Hz 

45 ms 

17 Hz 

135 ms 

4 Hz 

495 ms 

Input Group to System Isolation 

Channel to Rack: 707 VDC for 1 minute   Optical and 
magnetic Channel to Channel: Input channels are 
differential as long as all pins are within 13 V dc of the 
output return lines. 

Module Power LED 

On: indicates power is applied and module not faulted. 

                                                      
 
 
 

5

  The  module  update  time  is  purely  the  sum  of  conversion  times  for  each  enabled  channel.  The  extra 

addition of 1 is not necessary. 

Содержание 1762sc-IF4OF4

Страница 1: ......

Страница 2: ...or service referenced herein No patent liability is assumed by Spectrum Controls Inc with respect to the use of any of the information products circuits programming or services referenced herein The...

Страница 3: ...rations 2 2 2 3 1 Prevent Electrostatic Discharge 2 3 2 3 2 Remove Power 2 3 2 3 3 Selecting a Location 2 3 SECTION 2 4 MOUNTING 2 4 2 4 1 Minimum Spacing 2 4 2 4 2 DIN Rail Mounting 2 4 2 4 3 Panel M...

Страница 4: ...to install configure program operate and troubleshoot a control system using the 1762sc IF4OF4 Related Documentation The table below provides a listing of publications that contain important informati...

Страница 5: ...pe is used for emphasis Bold type identifies headings and sub headings WARNING Identifies information about practices or circumstances that can lead to personal injury or death property damage or econ...

Страница 6: ...vi MicroLogix 1200 Analog Combo Module 4Ch IN 4Ch Out User s Manual Pub 0300247 01 Rev D...

Страница 7: ...iption The combo supports current voltage and thermocouple input types and current or voltage output types The module digitally converts and stores analog data from any of the three input types mentio...

Страница 8: ...and Ranges The table below lists the input types and their associated ranges Table 1 2 Input Types Input Type Range E Type Thermocouple 200 to 1000 C 328 to 1832 F J Type Thermocouple 180 to 1200 C 2...

Страница 9: ...ferent filter frequencies 4 Hz 17 Hz 62 Hz 470 Hz Section 1 6 Hardware Features Channels are wired as differential inputs or single ended outputs One cold junction compensation CJC sensor comes instal...

Страница 10: ...l latch 9 Pull loop 10 Ch 6 and Ch 7 DIP switch Voltage Current selection Shipped with current selected DIP switches in Down position as shown 1 6 1 LED Indicator The 1762 combo module uses a single g...

Страница 11: ...or input output data not valid condition If such a condition is detected the channel data value will fail to a user defined state defined in the module configuration settings For more details refer to...

Страница 12: ...1 6 Chapter 1 Module Overview User s Manual Pub 0300247 01 Rev D See the block diagram below ASIC...

Страница 13: ...EMC and the following standards in whole or in part documented in a technical construction file IEC 61000 6 4 Electromagnetic compatibility EMC Part 6 4 Generic standards Emission standard for indust...

Страница 14: ...components may impair suitability for Class I Division 2 Touch a grounded object to discharge static potential Do not replace components or disconnect equipment unless power has been switched off or...

Страница 15: ...signal to your system s field devices causing unintended machine motion Causing an explosion in a hazardous environment Electric arcing causes excessive wear to contacts on both the module and its ma...

Страница 16: ...50 8 mm 2 in of space on all sides for adequate ventilation as shown Figure 2 1 NOTE 1762 expansion I O may only be mounted horizontally WARNING During panel or DIN rail mounting of all devices be su...

Страница 17: ...th extreme vibration and shock concerns use the panel mounting method described below instead of DIN rail mounting 2 4 3 Panel Mounting Use the dimensional template shown below to mount the module The...

Страница 18: ...and the bus connector cover must be snapped in place In Class I Division 2 applications all modules must be mounted in direct contact with each other as shown in the graphic If DIN rail mounting is us...

Страница 19: ...itter specifications Outputs Load resistance for a voltage output channel must be equal to or greater than 1 K Load resistance for a current output channel must remain between 0 and 500 Grounding WARN...

Страница 20: ...ny other wiring and as far as possible from sources of electrical noise such as motors transformers contactors and ac devices Generally allow at least 15 2 cm 6 in of separation for every 120 V of pow...

Страница 21: ...re under the terminal pressure plate You can use the stripped end of the wire or a spade lug The terminals will accept a 6 35 mm 0 25 in spade lug See Figure 2 5 3 Tighten the terminal screw making su...

Страница 22: ...o module uses a single green LED to show operational status of the module The table below shows the possible blink codes Blink Code Description Blinks rapid green The module is not in run mode Solid G...

Страница 23: ...You Should Know This chapter describes how to configure the IF4OF4 module for the MicroLogix 1100 1200 and 1400 system using RSLogix 500 programming software Section 3 2 Module Memory Map The module u...

Страница 24: ...e describes how to add the IF4OF4 module to the RSLogix 500 programming software 1 Create a new RSLogix 500 project and select either a Micro 1100 1200 or 1400 processor 2 Double click I O Configurati...

Страница 25: ...le within RSLogix 500 3 4 1 Output Data File Configuration Data The output data file is used to configure the advanced settings of the module including input type output type data format filter settin...

Страница 26: ...on Register Input 2 High byte Channel 5 Configuration Register Input 2 O e 7 Low byte Channel 6 Configuration Register Input 3 High byte Channel 7 Configuration Register Input 3 1 See Table 3 2 2 See...

Страница 27: ...67 11000 17202 11000 10 00 VDC High Range 29788 10000 16383 10000 10 00 VDC Low Range 29788 10000 0 10000 11 00 VDC Low Limit 32768 11000 819 11000 0 to 5 V 5 50 VDC High Limit 32767 5500 18021 11000...

Страница 28: ...g F 1 3 4 4 Input Channel Configuration Channels 6 and 7 Channels 6 and 7 can be configured for current or voltage including thermocouple inputs The following table describes the configuration options...

Страница 29: ...formats may yield the highest effective resolutions but may also require that you convert channel data to real engineering units in your control program Table 3 6 Input Channel Data Ranges Input Range...

Страница 30: ...VDC High Range 10000 1000 32767 16383 10 00 VDC Low Range 10000 1000 32768 0 11 00 VDC Low Limit 11000 1100 32768 819 0 10 V 11 00 VDC High Limit 11000 1100 32767 17202 10 00 VDC High Range 10000 100...

Страница 31: ...ut file is shown below Table 3 7 Input Data File Layout Word Bits 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 General Status I e 0 S7 S6 S5 S4 S3 S2 S1 S0 Output Status I e 1 LD3 U3 O3 LD2 U2 O2 LD1 U1 O1 L...

Страница 32: ...nt depending on the output type up to the High Limit value LD Load Error This applies only to output channels If the channel is configured for voltage this bit indicates a short circuit If configured...

Страница 33: ...62 Hz 14 Hz 45 ms 17 Hz 4 Hz 135 ms 4 Hz 1 Hz 495 ms Getting Technical Assistance Note that your module contains electronic components which are susceptible to damage from electrostatic discharge ESD...

Страница 34: ...3 12 Chapter 3 Configuring the 1762sc IF4OF4 for RSLogix 500 User s Manual Pub 0300247 01 Rev D...

Страница 35: ...0 030 in max peak to peak Shock Operating 30 G Bus Current Draw max 30 mA at 5 VDC Max 3 4 W Max 140 mA max at 24 V Heat Dissipation 3 0 W Total Max Resolution 16 bits Integer Format Channel Update T...

Страница 36: ...1 C UL under CSA C22 2 No 213 Operating Temperature Code T4a Radiated and Conducted Emissions EN61131 2 Electrical EMC The module has passed testing at the following levels ESD Immunity IEC61000 4 2 4...

Страница 37: ...lters Normal Mode Rejection 4 Hz Filter 74 dB minimum at 50 and 60 Hz 17 Hz Filter 65 dB minimum at 50 and 60 Hz 62 Hz Filter First notch at 31 Hz typically 30 dB 470 Hz Filter First notch at 237 Hz t...

Страница 38: ...mum System accuracy at 20 60 C 4 and 17 Hz filters Type J 180 C to 1200 C 5 0 degrees C maximum Type K 200 C to 1370 C 6 0 degrees C maximum Type E 200 C to 1000 C 4 5 degrees C maximum Type T 190 C t...

Страница 39: ...acy at 25 C 4 and 17 Hz filters 20 uA maximum for 0 20 mA inputs 20 uA maximum for 4 20 mA inputs System accuracy at 20 C 60 C 4 and 17 Hz filters 50 uA maximum for 0 20 mA inputs 50 uA maximum for 4...

Страница 40: ...es Current Output 380 nA per bit when using RAW format for all current ranges Differential Nonlinearity 1 LSB see resolution for LSB size Output Ripple 15 mV ripple for voltage or current Output Imped...

Страница 41: ...Appendix A Module Specifications A 7 User s Manual Pub 0300247 01 Rev D...

Страница 42: ...A 8 Appendix A Module Specifications User s Manual Pub 0300247 01 Rev D...

Страница 43: ...tive 2 1 F Filter Frequencies 1 3 G Grounding 2 7 H Hazardous Location 2 2 I Input Data 3 9 Input Type 1 1 L LED 1 4 2 10 M Memory Map 3 1 Module Update Time 3 11 Mounting DIN 2 4 Panel 2 5 N Noise 2...

Страница 44: ...User s Manual Pub 0300247 01 Rev D...

Страница 45: ...User s Manual Pub 0300247 01 Rev D...

Страница 46: ...ions subject to change without notice The Encompass logo and ControlLogix are trademarks of Rockwell Automation Corporate Headquarters Spectrum Controls Inc P O Box 6489 Bellevue WA 98006 USA Fax 425...

Отзывы: