SharpEye
TM
IR3 Flame Detector User Guide
82
Air Shield
D.6
Air Shield
The air shield (P/N 777650) is suitable for use with the SharpEye 40/40
Series Optical Flame Detector 40/40I, for both the aluminum and st.st.
enclosures.
Optical flame detectors are often used in highly polluted or dirty areas that
force maintenance personnel to access the detector frequently in order to
clean its optical window. The special air shield, developed for SharpEye
40/40 series optical flame detectors, allows their installation under
environmental conditions where they may be exposed to oil vapors, sand,
dust, and other particulate matter.
The temperature of the air supply to the air shield should not exceed
60°C/140°F at any time.
Air pressure source:
Clean, dry, and oil-free air
Pressure:
2
–
3 bar / 30
–
45 psi
Fitting:
7/16
”
–
20UNF-2A
Operation Temperature:
–
55°C to +85°C /
–
67°F to +185°F
For more instructions, refer to TM777650.
Figure 21: Air Shield
Содержание SharpEye 40/40I
Страница 2: ...www acornfiresecurity com www acornfiresecurity com ...
Страница 12: ...www acornfiresecurity com www acornfiresecurity com ...
Страница 32: ...www acornfiresecurity com www acornfiresecurity com ...
Страница 46: ...www acornfiresecurity com www acornfiresecurity com ...
Страница 54: ...www acornfiresecurity com www acornfiresecurity com ...
Страница 55: ...Appendix 55 Appendix www acornfiresecurity com www acornfiresecurity com ...
Страница 56: ...www acornfiresecurity com www acornfiresecurity com ...
Страница 64: ...www acornfiresecurity com www acornfiresecurity com ...
Страница 72: ...www acornfiresecurity com www acornfiresecurity com ...