TM 40/40I, Rev (14) February 2017
Performance Considerations
21
1.4.5.6 TR CU/EAC
The 40/40I Flame Detector is in compliance with the standard TR CU
012/2011 per:
1Ex d e IIC T5 Gb X
Ex tb IIIC T96°C Db X
–
55°C
≤
Ta
≤
+75°C
or
1Ex d e IIC T4 Gb X
Ex tb IIIC T106°C Db X
–
55°C
≤
Ta
≤
+85°C.
For more details, see TR CU certificate No. Т
R CU C-
US.МЮ62.В.04333.
1.5
Performance Considerations
This section describes performance aspects of the 40/40I and includes:
Detection Sensitivity, page 21
Cone of Vision, page 22
False Alarm Prevention, page 24
Visual Indicators, page 25
Output Signals, page 26
Detector Status, page 27
Auxiliary Relay as End-of-Line, page 28
1.5.1 Detection Sensitivity
Detection sensitivity is the maximum distance at which the detector reliably
detects a specific size of fire and typical type of fuel (standard fire).
1.5.1.1 Standard Fire
Defined as a 1ft
2
/0.1m
2
n-heptane pan fire, with maximum wind speed of
6.5ft/sec / 2m/sec.
1.5.1.2 Sensitivity Ranges
The detector has 4 user-selectable sensitivity ranges. For each range there
are 2 response levels:
Warning (Pre-alarm)
Alarm
The detection distance for the Warning level is approximately 10% higher
than for the alarm distance.
Содержание SharpEye 40/40I
Страница 2: ...www acornfiresecurity com www acornfiresecurity com ...
Страница 12: ...www acornfiresecurity com www acornfiresecurity com ...
Страница 32: ...www acornfiresecurity com www acornfiresecurity com ...
Страница 46: ...www acornfiresecurity com www acornfiresecurity com ...
Страница 54: ...www acornfiresecurity com www acornfiresecurity com ...
Страница 55: ...Appendix 55 Appendix www acornfiresecurity com www acornfiresecurity com ...
Страница 56: ...www acornfiresecurity com www acornfiresecurity com ...
Страница 64: ...www acornfiresecurity com www acornfiresecurity com ...
Страница 72: ...www acornfiresecurity com www acornfiresecurity com ...