Entry/Exit Port Slider Replacement Guide
26
Picker-Slot Calibration
1.
From the Available Tests list, select
Picker Slot Calibration: Long Axis
(as shown in
2.
Select
Prepare Test
.
3.
Select
Run Test
(there are no parameters for this test).
This test will calibrate the top and bottom location of each tape pack by loading
the tape in Slot 1 and Slot 15 of each data cartridge magazine.
4.
Watch to see that each first and fifteenth slot loads correctly.
The tape will be returned to the E/E port when the test is completed.
Note:
This test takes a long amount of time to complete. It could take up
to an hour in a fully-loaded Spectra 64K library.
5.
Check the test results.
The test may indicate that retries were made, which is normal.
Caution:
Make sure that there are no slots that
fail
to load. If a slot fails,
contact Spectra Logic Technical Support at (800) 227-4637 or at
(303) 449-0160.
6.
Return to the Inventory screen.
7.
Select
Open/Close
to open the E/E port.
8.
Remove the tape from the library.
9.
Select
Open/Close
to close the E/E port.