Gripper Jaws Replacement Guide for Spectra Logic Libraries

Prepare the Library and Host System

Remove tapes from the library

Some tapes will interfere with replacing the gripper jaws and need to be temporarily removed from the library. 
Use the host backup software or the library front panel interface to remove the following tapes from the 
library. 

Shut down the library and the host system

1. Perform a complete system shut down. Exit all programs running on the host computer and switch 

OFF

 power to the host computer, the library, and any other attached equipment. 

Warning: 

Electrical shock hazard inside the library can cause injury or death. Disconnect the 

AC power to the library before removing the cover. Never connect the AC power to 

the library with the cover removed.

Warning: 

Possible visible laser light source inside the library can cause serious, permanent eye 

injury. Never connect the AC power to the library with the cover removed. 

2. Disconnect all cables from the library.

• Disconnect the AC power cord from the wall outlet and the rear of the library.
• Disconnect the SCSI cables from the rear of the library.
• If applicable, disconnect the serial cable(s) from the RS–232 port(s) on the rear of the library.

3. If necessary, move the library to a location where you have access to all sides of the library. 

Warning: The library is heavy, about 56 pounds. Get help when moving the library.

Spectra 4000, 5000 and 5100

4mm Tape Libraries

20 slot carousel

40 slot carousel

60 slot carousel

Tape slots to be 

emptied

4 and 5 

6 through 10

8 through 15

Spectra 9000 and 10000

8mm Tape Libraries

20 slot carousel

40 slot carousel

Tape slots to be 

emptied

5 through 8

9 through 14

Содержание 90841625

Страница 1: ...Gripper Jaws Replacement Guide Part Number 90840098 Revision C Gripper Jaws Replacement Guide for Spectra Logic Libraries Gripper Jaws Replacement Guide for Spectra Logic 4000 10000 Libraries...

Страница 2: ...UPTION OF BUSINESS OR FOR INDIRECT SPECIAL INCIDENTAL OR CONSE QUENTIAL DAMAGES OF ANY KIND EVEN IF SPECTRA LOGIC CORPORATION HAS BEEN ADVISED OF THE POSSIBILITY OF SUCH DAMAGES ARISING FROM ANY DEFEC...

Страница 3: ...d use the jaws lose their ability to grip and hold the tapes and need to be replaced The two gripper jaws on the picker arm are different It is recommended that you remove and replace one jaw at a tim...

Страница 4: ...AC power to the library with the cover removed Warning Possiblevisiblelaserlightsourceinsidethelibrarycancauseserious permanenteye injury Never connect the AC power to the library with the cover remov...

Страница 5: ...rary frame Flat blade screws must be completely removed from the library If the library is a horizontal unit three screws hold the cover in place If the library is a vertical unit four screws hold the...

Страница 6: ...mb on the solenoid back plate and squeeze This unlocks the picker arm See Figure 6 for the location of these parts and Figure 7 and for the position of your thumb an index finger 3 Push the picker arm...

Страница 7: ...n page 8 shows the gripper jaws their locations and the part numbers for each jaw for the 4mm and 8mm libraries 1 Use the 1 phillips screwdriver to remove the two phillips screws that hold the gripper...

Страница 8: ...e long tooth along the entire edge of the jaw Figure 12 shows the common gripper jaw piece used in both 4mm and 8mm libraries See Figure 9 for the location of the jaw pieces on the gripper arm Figure...

Страница 9: ...screws first with a few turns before you tighten any of them with the screwdriver Doing it this way insures that all the holes on the cover will meet the screw holes on the library Return the library...

Страница 10: ......

Отзывы: