UV Coil Sterilisation, ALP, Issue 1

2. Technical data

SIL Models

Length

Wattage

Voltage

UV Output @10”

(inches)

(W)

(V)

(µW/sq.cm.)

SIL 64

64

108

165

1618

SIL 48

48

83

165

1520

SIL 36

36

63

80

1446

SIL24

24

48

65

1258

SIL18

18

36

55

900

SIL12

12

26

33

500

3. Unit content

The SIL UV sterilisation unit is comprised of three 

main components: 
1. UV Lamp plus mounting clips and reflector.
2. Connecting cable, plug and protective boot.
3. Control Ballast.

Note:

 Depending on the installation; the ballast 

may be supplied: 
a. Loose; for fitting inside the control panel
OR
b. Installed either singly or in multiples within a 

sealed aluminium enclosure.

OR
c.  Within a separate control panel. The control 

panel may provide optional extra features such 

as ON/OFF control, BMS connectivity, run-time 

counter and lamp failure indication depending 

on the unit specification. 

d. Optional installation fixtures are also available to 

order for fitting the UV lamp assembly inside the 

AHU.

N.B. Installation:

 In every case the unit should 

be installed by suitably qualified and trained 

personnel.

The Germicidal UV Lamp and reflector should be 

installed so that the lamp is facing the coil. 
Lamps may be installed either Upstream or 

Downstream of the coil depending on the available 

space and orientation of the equipment. Lamps 

should be positioned as indicated on the drawing 

provided by SPC. 
Ideally the coil should be mounted 10-12 inches 

from the face of the coil. Do not mount the lamp 

closer than 4’’ (100 mm) from the coil face.
After Installing the lamp fitting, insert the lamp into 

the clips provided. Connect the 4-pin socket to the 

pins at one end of the lamp and push the boot 

around the end of the lamp. 

N.B:

 Do not touch the UV lamp without gloves. 

Always clean the lamp surface with a dry cloth 

after installation. 
Connect the lamp cable to the control ballast using 

the connector provided. 
Turn off all power to the unit before connecting 

the ballast box to a fused and switched 220-240v 

power supply. This supply must be broken by a 

micro-switch (by others) on the AHU access door. 

Warning Labels:

 to be fixed outside of the AHU

Содержание ALP Series

Страница 1: ...UV Coil Sterlisation Installation operation maintenance instructions ALP Series SPC Heat Pipes FZC...

Страница 2: ...This manual describes the characteristics of the equipment at the current time therefore it may not capture later technological improvements introduced by SPC as part of its constant endeavour to enha...

Страница 3: ...performing maintenance or service Personal injury may result if this is not done Do not touch the lamp glass without gloves or reduced performance of the lamp may result Clean lamps with a dry cloth...

Страница 4: ...AHU N B Installation In every case the unit should be installed by suitably qualified and trained personnel The Germicidal UV Lamp and reflector should be installed so that the lamp is facing the coil...

Страница 5: ...en key set 2 Screw driver 3 Electric tester Steps to follow for installation of optional fixtures 1 Fit the angles on the Aluminium channels with the help of screws provided Refer figure a b Figure a...

Страница 6: ...e 5 Operation The UV Coil cleaning lamp is designed to operate for its rated hours of continuous use The lamp should be wired to operate even when the fan is not running to ensure the coil is kept cle...

Страница 7: ...7 7 Wiring Diagram WHITE P BLACK N 230 V AC BALLAST 5 4 3 2 2 1 1 Lamp 12inch 36inch HO 800 mA WHITE P BLACK N 230 V AC BALLAST 5 4 3 2 2 1 1 Lamp 46inch 64inch HO 800 mA Red 1 2 3 4 Yellow 5...

Страница 8: ...SPC Heat Pipes FZC P O BOX 50816 Dubai UAE T 971 4 3341178 E spcoils spcoils ae www spcoils ae UV Coil Sterilisation ALP Issue 1 SPC Heat Pipes FZC...

Отзывы: