background image

6

LIGHT LEVEL TEST TABLE

The green LED will blink according to the energy produced by the solar cell

blinks

lux                        foot candles

time to fully charge

    discharge time

0,1

< 15                            < 1.4

below operating level

n/a

2

15-50                             1.4  - 4.6

min operating level

n/a

3

50-100                           4.6 - 9.3

24 hours to full charge

100 hours

4

100-200                         9.3 - 18.6

12 hours to full charge

150 hours

5

200-400                       18.6 - 37.2

6 hours to full charge

200 hours

The time to fully charge is based on the storage capacitor charging from 

a  non-operational  condition.  Discharge  time  indicates  how  long  a  fully 

charged sensor will operate in the dark.  The test will repeat every 2 sec-

onds and run for a duration of 100 seconds. You may quit the test at any 

time by pressing the test button for 6 seconds.

Range Confirmation Test:

   provides visual feedback of the sensors signal 

strength by a linked receiver with range confirmation capability (only  “F        

series” controllers have range confirmation ability). One and only one re

-

ceiver can be linked to the sensor for proper operation of the test.  (disable 

repeaters in range for proper test operation).

1. 

To enter Range Confirmation Test mode, press and hold the occupan

-

cy/test button for 6 seconds. The green led will begin to blink.

2. 

A quick press and release of the button at this point will allow you to 

select between light level test (green LED) and range confirmation test 

(amber). When the amber LED is blinking, go to step 3. 

(If the 3 LEDs 

fail to blink during this test, insert a battery or place under a lamp with 

at least 100 fc (1000 lux) for 1 hour before retrying.)

3. 

Press and hold the test button again for 6 seconds to select Range 

Confirmation Test. 

All three LED’s can blink in this test mode when the sensor transmits or 

receives a Range Confirmation Telegram. The sensor will display the signal 

strength status for 5 seconds, see table below.

      

RANGE CONFIRMATION TEST TABLE

LED

Signal Strength

Green

> -70 dbm 

Amber

> -80 dbm

Red

< -80 dbm

The test will repeat every 10 seconds and run for a duration of 3      min

-

utes. You may quit the test at any time by pressing the occupancy/test  

button for 6 seconds.

Содержание WT913G

Страница 1: ...or product family includes WT913G NL Temperature Sensor Setpoint NOTE The WT913G is a solar powered device that absorbs solar energy storing it for use during low light periods Before assigning the RT...

Страница 2: ...ed to provide temperature control in the space that the sensor is monitoring for closed loop temperature control The sensor and receiver must be within range preferably in the same room ing 50 15 2 m...

Страница 3: ...tton RTS 2HS models only Users can override a room occupancy state by pressing the occupancy button on the lower right edge of the sensor LED Operation LEDs are on the right side of the solar panel Th...

Страница 4: ...place Linking the Temperature Sensor to a Receiver This process requires the controller or receiver to be mounted and pow ered and within range of the temperature sensor to be linked The sensor is a...

Страница 5: ...ttery holder and press the clip in with your finger Test Operating Modes Ensure the RTS is fully charged or insert a battery before entering test modes The following tests can be selected when in test...

Страница 6: ...nd only one re ceiver can be linked to the sensor for proper operation of the test disable repeaters in range for proper test operation 1 To enter Range Confirmation Test mode press and hold the occup...

Страница 7: ...r 0 10 Glass 0 10 Brick 5 35 MDF 5 35 Ferro concrete 10 90 Metal 90 100 Aluminum 90 100 Material Radio Range typical Line of sight 80 24m corridors Line of sight 150 46m open halls Plasterboard 80 24m...

Страница 8: ...300U The enclosed device complies with Part 15 of the FCC Rules I this device may not cause harmful interference and ii this device must accept any interference received including IC RSS 210 315MHz an...

Отзывы: