background image

3

Temperature Sensing Operation

Temperature and Humidity Monitoring

 - The temperature sensor will 

record the temperature, temperature set point and humidity values* 

every 10 seconds (sample period) when there is approximately 100 lux 

(10 foot-candles) available. If there is less than 100 lux (10 fc), the sam

-

ple period will increase to 100 seconds. After 24 hours at < 15 lux (1.5 

fc) the sample period will increase to 200 seconds. *Assuming sufficient 

storage charge to operate.

Temperature Set Point

 - Users can adjust the temperature set point by 

rotating the knob counterclockwise to lower the set point value; clock

-

wise to increase the set point value. 

The receiving temperature control equipment must scale the set point 

range to values that are applicable for the application.

Fan Speed Switch 

- Users can adjust the fan speed switch by sliding the 

switch to a setting: Auto, OFF, Low (1) Med (2), High (3).

Occupancy Button

 - (RTS-2HS models only) Users can override a room 

occupancy state by pressing the occupancy button on the lower right 

edge of the sensor.                                                                       

LED Operation - 

LEDs are on the right side of the solar panel. The  red 

LED will flash when the Link or Occupancy button is pressed.  See Test 

Operating Modes for further LED information.

Transmitting Values

 - The temperature sensor will transmit  a  telegram 

when:

• 10 sample periods have been completed or

when the fan switch or occupancy button are used or

when the temperature value difference from the last transmitted

value is greater than 0.3°C, (0.5°F) or

the humidity value difference from the last transmitted value is

greater than 3%.

Installing the Temperature Sensor 

The temperature sensor can be mounted on any surface; glass, stone, 

concrete, wallboard, cubicle partitions, etc. The sensor can be mounted 

using screws (not supplied) through the removable back plate (2 key-

holes or using double sided tape or Velcro™ (not supplied). 

The mounting location of the wireless transmitter is important as this 

will  directly  affect  the  receivers  reception  of  the  telegrams.  Before        

Содержание WT912G

Страница 1: ...mily includes WT912G NL Temperature Sensor WT913G NL Temperature sensor Setpoint NOTE The WT912G WT913G are solar powered devices that absorbs solar energy storing it for use during low light periods Before assigning the RTS device to a receiver controller the device should be exposed to a good light source for a minimum of 2 hours INSTALLATION GUIDE ...

Страница 2: ... temperature control in the space that the sensor is monitoring for closed loop temperature control The sensor and receiver must be within range preferably in the same room ing 50 15 2 m range greater care must be taken to insure proper re Even with a brief exposure to light the sensor will operate however for e h t n i a t n o c t a h t s m a r g e l e t s u t a t s s t i m s n a r t r o s n e s ...

Страница 3: ...utton RTS 2HS models only Users can override a room occupancy state by pressing the occupancy button on the lower right edge of the sensor LED Operation LEDs are on the right side of the solar panel The red LED will flash when the Link or Occupancy button is pressed See Test Operating Modes for further LED information Transmitting Values The temperature sensor will transmit a telegram when 10 samp...

Страница 4: ...n place Linking the Temperature Sensor to a Receiver This process requires the controller or receiver to be mounted and pow ered and within range of the temperature sensor to be linked The sensor is a solar powered device that absorbs energy through a so lar panel storing it for use during low light periods Before assigning the sensor to a receiver controller the device must be exposed to a good 1...

Страница 5: ...attery holder and press the clip in with your finger Test Operating Modes Ensure the RTS is fully charged or insert a battery before entering test modes The following tests can be selected when in test mode Light Level Test provides visual feedback of the immediate energy produced by the solar panel 1 To enter Light Level Test mode press and hold the occupancy test button for 6 seconds The green L...

Страница 6: ...and only one re ceiver can be linked to the sensor for proper operation of the test disable repeaters in range for proper test operation 1 To enter Range Confirmation Test mode press and hold the occupan cy test button for 6 seconds The green led will begin to blink 2 A quick press and release of the button at this point will allow you to select between light level test green LED and range confirm...

Страница 7: ...er 0 10 Glass 0 10 Brick 5 35 MDF 5 35 Ferro concrete 10 90 Metal 90 100 Aluminum 90 100 Material Radio Range typical Line of sight 80 24m corridors Line of sight 150 46m open halls Plasterboard 80 24m through 3 walls Brick 33 10m through 1 wall Ferro concrete 33 10m through 1 wall Ceiling not recommended Wireless System Layout Hints Avoid locating transmitters and receivers on the same wall Avoid...

Страница 8: ...The enclosed device complies with Part 15 of the FCC Rules I this device may not cause harmful interference and ii this device must accept any interference received including IC RSS 210 315MHz and 902 MHz models only ISO 9001 only 315 MHz models that bear a MIC mark Law Compliance This device is granted pursuant to the Japanese Radio Law 電波法 電気通信事業法 number will become invalid telephone Toll Free 1...