– 10 –
Split Inverter Air-to-Water Heat Pump
When mulitple outdoor units are installed, attention should be paid to their arrangement so as to ensure that the space around the
outdoor units does not affect the installation of return air, air outlet, system piping, and other devices. The following arrangement is
for reference:
Figure 3.3 Installation space for single outdoor unit (inches)
Figure 3.4 Installation space for multiple outdoor units (inches)
Do not block the air outlet of the outdoor unit.
Clearances
26
Installation Instructions
Unit Installation
The outdoor unit can be installed separately or in multiple. When mulitple outdoor units are
installed, attention should be paid to their arrangement so as to ensure that the space around
the outdoor units does not affect the installation of return air, air outlet, system piping, and
other devices. The following arrangement is for reference:
Installation space for single outdoor unit
:
(
unit
:
mm
)
>500
>500
>1000
Unconfined space
Installation space for multiple outdoor units
:
(
Unit
:
mm
)
>500
>1000
>1000
>800
>400
>400
>400
Air out
Air out
Air out
>3000
Do not cover the air outlet of the outdoor unit;
If there are objects stacked around the outdoor unit, its height should be
at least 400 mm lower than the top of the unit;
When installed in a small room, certain measures should be taken to
prevent the leakage of refrigerant. Once leakage volume exceeds the
limit concentration, it may cause suffocation.
Installation
space
Unit Installation
>20
>20
>20
>20
>72
>40
>40
>40
E
B>72inch ;
E=see note 1
Note:
The base of the unit should be located above winter snow
level to allow proper drainage of condensate. The condensate
should be provided a path to drain before refreezing in an area
that could create an obstruction or hazardous conditions such as
on a walkway.