SIM Inverter Monobloc Air-to-Water Heat Pump
Top Menu Code
Description
Units
Range
Passcode -036 -060
Notes
Temp
R01 Hot Water Setpoint
Deg F R06 to R07
22
140
140 DHW Setpoint. Cannot be less than R06 or
greater than R07
R02 Heating Setpoint
Deg F R08 to R09
22
120
120 Return temperature setpoint in heating. Must fall
between R10 & R11
R03 Cooling Setpoint
Deg F R10 to R11
22
46.4 46.4 Return temperature setpoint in Cooling. Must fall
between R08 & R10
R04 Power-on return Difference Deg F
0.9 to 18
22
3.6
3.6 Differential from setpoint to start compressor
operation
R05 Standby Temp Difference
Deg F
0 to 18
66
3.6
3.6 Differential from setpoint to end compressor
operation
R06 Min Hot Water Setpoint
Deg F 32 to R07
66
104
104 Minimum value allowed for DHW setpoint
R07 Max Hot Water Setpoint
Deg F R06 to 149
66
140
140 Maximum value allowed for DHW setpoint
R08 Min Heating Setpoint
Deg F
68 to 86
66
86
86 Minimum value allowed for Heating setpoint
R09 Max Heating Setpoint
Deg F 86 to 140
66
120
120 Maximum value allowed for Heating setpoint
R10 Min Cooling Setpoint
Deg F 46.4 to 68
66
46.4 46.4 Minimum value allowed for Cooling setpoint
R11 Max Cooling Setpoint
Deg F
68 to 86
66
68
68 Maximum value allowed for Cooling setpoint
R12 Electric Heating
-
0 to 2
22
0
0
0=No Elect. heater, 1=Heater in HP Circuit,
2=Heater in DHW tank
R13 Electric Heat Start
Difference
Deg F
0 to 18
66
9
9
Electric Heat is active when the water temp is
below R02-R13
R14 Electric Heat Start AT
Deg F
14 to 86
66
41
41 Electric Heat is active after delay when the Amb
Temp is below R14
R15 Delay of Electric heater
Min.
0 to 60
66
5
5
Delay of electric heat start when
Amb Temp is between R14 and R16
All these must be true, and compressor must be at >80Hz, for
Electric heat to energize
R16 Electric Heat start at once
AT
Deg F
-22 to 68
66
25
25 Electric Heat is active immediately when Ambient
Temp is below R16
R17 Compensatation ON, Low
AT
Deg F R18 to 32
66
17
17 Low Ambient T Heating Temp rollback ends on
fall at this Ambient T
R18 Compensatation OFF, Low
AT
Deg F -22 to R17
66
10
10 Low Ambient T Heating Temp rollback ends on
fall at this Ambient T
R19 Low AT Maximum
Compensation
Deg F 68 to 140
66
110
110 Resulting Water Temp rollback at R18 Ambient T
R20 Compensation ON High AT Deg F
23 to 50
22
23
23 OD reset begins to lower Water Temp as Ambient
rises to this point
R21 Compensation OFF High AT Deg F 23 to 140
22
50
50 OD reset completes lowering Water Temp as
Ambient rises to this point
R16 High AT Max Compensation Deg F 68 to 140
66
110
110 Resulting Water Temp rollback at R21 Ambient T
See graphic
High Temp
Disinfection
G01 Setpoint
Deg F 140 to 158
22
158
158 Target temperature of Sterilize mode.
G02 Time of Duration
Min.
0 to 60
22
0
0
Time that Sterilize Temp is held during cycle. If 0,
feature is disabled
G03 Time
Hr
1 to 23
22
0
0
Time of day (whole hour, 24 hr clock) to start
Sterilize
G04 Sterilize Cycle
Day
1 to 30
22
7
7
Interval, in days, between Serilize Cycles
Requires electric heat if G01 is greater than R01
Содержание CSOLSTICE SIM-036
Страница 49: ...49 SIM Inverter Monobloc Air to Water Heat Pump SECTION 7 TROUBLESHOOTING Possible Cause Possible Solution...
Страница 51: ...51 SIM Inverter Monobloc Air to Water Heat Pump SECTION 8 REPLACEMENT PARTS SIM036...
Страница 52: ...52 SIM Inverter Monobloc Air to Water Heat Pump Replacement Parts SIM036...
Страница 53: ...53 SIM Inverter Monobloc Air to Water Heat Pump Replacement Parts SIM060...
Страница 54: ...54 SIM Inverter Monobloc Air to Water Heat Pump Replacement Parts SIM060...
Страница 59: ...59 SIM Inverter Monobloc Air to Water Heat Pump...