Page 13 of 22
Installation & Adjustment Procedures
Insulator Preload
1. When the contact engagement is correctly set, preload the insulators toward the center of the
gap. Add one flat on both outside jack screw nuts and subtract one flat on both inside nuts
). This is done on both bearings.
To add, turn the nuts clockwise (facing down). To subtract, turn the nuts counter-clockwise.
Figure 11: Preload Insulators