Power Requirements for Sourcefire Devices
3D7010/7020/7030
Appendix A
Static Control
C
AUTION
!
Electrostatic discharge control procedures, such as using grounded wrist
straps and an ESD work surface, must be in place before unpacking, installing, or
moving the appliance. Excessive electrostatic discharges can damage the
appliance or cause unintended operation.
3D7010/7020/7030
The 3D7010/7020/7030 (CHRY-1U-AC) is suitable for installation by qualified
personnel in network telecommunication facilities and locations where the
National Electric Code applies. Note that this device is available only as an AC
appliance.
Sourcefire recommends that you save the packing materials in case a return is
necessary.
For more information, see the following sections:
•
See
on page 241 for circuit installation, voltage, current,
frequency range, and power cord information.
•
See
Grounding/Earthing Requirements
on page 242 for bonding locations,
recommended terminals, and ground wire requirements.
Installation
The Sourcefire 3D System appliances must be installed in accordance with the
requirements of Article 250 of NFPA 70, National Electric Code (NEC) Handbook
and local electrical codes.
The appliance uses a single power supply. An external surge protection device
must be used at the input of the network equipment where the Sourcefire 3D
System is to be installed.
The circuit must be rated for the full rating of the appliance.
Voltage
The power supply works with 100VAC to 240VAC nominal (90VAC to 264VAC
maximum). Use of voltages outside this range may cause damage to the
appliance.
Current
The labeled current rating is 2A maximum over the full range. Appropriate wire
and breakers must be used to reduce the potential for fire.