Follow the Installation Instructions before proceeding. Set the 
thermostat mode to “OFF” prior to changing settings in setup 
or restoring Factory Defaults.

CAUTION

This thermostat has the ability to receive updates to its firmware. Periodically 
firmware updates are released by the manufacturer to add features and/or 
performance enhancements. This manual was produced reflecting the most 
current firmware/feature set at the time of publication, firmware rev. 12. Firmware 
releases after rev. 12 may not be adequately depicted in this manual. Please 
refer to the appropriate website or contact your place of purchase to learn about 
changes to the thermostat after firmware release 12.

Содержание S1-TBSU306-S

Страница 1: ...Owner s Manual Installation Instructions Optional accessories available including Wi Fi Digital Thermostat Commercial model S1 TBSU306 S Programmable with Humidity Control...

Страница 2: ...ally firmware updates are released by the manufacturer to add features and or performance enhancements This manual was produced reflecting the most current firmware feature set at the time of publicat...

Страница 3: ...in the air Icon The word or symbol that appears on the thermostat display Mode The current operating condition of the thermostat i e Off Heat Cool or Auto Non Programmable Thermostat A thermostat that...

Страница 4: ...dule 20 Service Filter 22 Runtimes 23 Time Period Programming 24 INSTALLER SETUP Setpoint Limits 26 Timers and Deadbands 27 Programming Fan Operation 28 Comfort Recovery Operation 28 Humidification De...

Страница 5: ...Know Your Thermostat Optional WiFi Module Backlit Scrolling Display Backlit LCD Display Heat or Cool Demand Indicator Red Heat Green Cool Backlit Cooler Warmer Buttons Setup Buttons Behind Door Overri...

Страница 6: ...2 Get To Know Your Thermostat Setup Buttons...

Страница 7: ...m temperature and displays the outdoor temperature when selected 5 Mode Indicators Selects the operational mode of the equipment HEAT Indicates the heating mode COOL Indicates the air conditioning mod...

Страница 8: ...ode 10 Desired SetTemperature Indicates desired room temperature s Also displays the highest and lowest temperatures for the day 11 Wi Fi icons One dot indicates the thermostat recognizes the wireless...

Страница 9: ...Indicates 2nd stage electric strip heat is being used when the thermostat is programmed for Heat Pump operation Only the Aux icon will appear during Cool to Dehumidify to indicate Reheat operation 16...

Страница 10: ...buttons Press the SET CLOCK button to confirm settings NOTE To adjust the time by hours press and hold the FAN button while pressing the WARMER or COOLER buttons Selecting the Heat or Cool Mode Selec...

Страница 11: ...e and will only turn on during a heat or cool demand The fan is forced into auto mode when running the program and the thermostat shows unoccupied Using the Override Button Unoccupied Operation During...

Страница 12: ...oor Humidity Sensor IMPORTANT Allow at least 2 minutes after the thermostat is powered on for the humidity to read correctly Press the HUMIDITY button then the mode button to display the current humid...

Страница 13: ...he power to the Heating Air Conditioning system at the main fuse panel Most residential systems have a separate breaker for disconnecting power to the furnace Remove the cover of the old thermostat If...

Страница 14: ...stall on the old thermostat Function new thermostat terminal marked connector marked G or F Fan G Y1 Y Cooling Y1 W1 W Heating W1 0 B Rh R M Vr A Power R C Common C O B Rev Valve W1 O B W2 2nd Stage H...

Страница 15: ...Aux output OUTDOOR Outdoor sensor SENSOR connections REMOTE Remote sensor SENSOR connections DRY Dry Contact CONTACT connections IMPORTANT This thermostat requires connection of both R 24 VAC Return...

Страница 16: ...sen the thermostat will energize the fan in heating 2 When GAS EL or HP is set for HP This switch GAS or ELEC defines the Aux Heat type When GAS is chosen the auxiliary heat will not be allowed to run...

Страница 17: ...ntial Commercial 1 Stage Cooling with 1 stage Electric Heat 5 Wire 1 Stage Cooling 1 Stage Heat 24VAC Power 24VAC Common 1st Stage Heat 1st Stage Cool Fan Residential Commercial 2 Stage Cooling with 3...

Страница 18: ...mpressor Stages Residential Commercial Heat Pump with O Reversing Valve 6 Wire 1 Stage Cooling 2 Stage Heat R 24VAC Power C 24VAC Common W1 O B Reversing Valve Y1 1st Stage Compressor Cool or Heat W2...

Страница 19: ...rol such as a sprinkler system DEHUM Dehumidification Terminal on Equipment Humidification System R G W1 O B W2 Y1 Y2 W3 DEHUM HUM C AUX REMOTE SENSOR OUTDOOR SENSOR DRY CONTACT R G W1 O B W2 Y1 Y2 W3...

Страница 20: ...nd cycle up through the heating stages Press COOLER to turn the heating stages off Press MODE to exit Press COOLER to turn on and cycle down through the cooling stages Press WARMER to turn the cooling...

Страница 21: ...and seven levels of brightness Night Dimmer setup step 5 Selecting On allows for automatic dimming of the display at night Night Dimmer Brightness setup step 6 The nighttime backlight can be adjusted...

Страница 22: ...entered Fast 12 00 12 00 WARMER COOLER MODE SETUP DISPLAY Press the SETUP button then press MODE repeatedly until the Scrolling Method setup step appears Use the WARMER or COOLER buttons to make selec...

Страница 23: ...onfirm your setting press the HOLIDAY button again When the thermostat is programmed for Holiday operation and the thermostat is in the Program On mode running an Occupied Unoccupied time period sched...

Страница 24: ...many of the wireless devices this status includes Battery Level Signal Strength and LastTime Updated If there is an optional wireless module installed the ACCESSORY SETUP button allows the user to li...

Страница 25: ...screens listed below a Wi Fi status connecting connected etc b Signal strength c Access point name d IP address e MAC address f Skyport status connecting connected with etc g Local API status Enabled...

Страница 26: ...rs of fan runtime in the Heating mode Cooling mode and in stand alone Fan operation Press FAN to reset Current Service Filter Calendar Days Setup Step 10 This counter displays the total number of cale...

Страница 27: ...4 This counter keeps track of the number of hours that the thermostat is overridden into Occupied settings Press FAN to reset UV Lamp Runtime setup steps 15 19 Current UV Lamp Calendar Days setup step...

Страница 28: ...heating or cooling depending on which one has been manually selected Auto Changeover is not available when this mode is selected Heat Only Allows the thermostat to only turn on HEAT or OFF modes Cool...

Страница 29: ...he mode for the occupied period The choices are Off Heat only Cool only and AUTO changeover Adjust the Occupied Cool Setpoint Press the Warmer or Cooler buttons to adjust the Cooling setpoint for comf...

Страница 30: ...r HVAC unit may energize For example at a setting of 6 cycles per hour the HVAC unit will only be allowed to energize once every 10 minutes The Cycles Per Hour limit may be overridden and reset by pre...

Страница 31: ...erence after the third stage turns on before the final stage of strip heat is activated 0 10 Minutes Between 1st and 2nd Stage setup step 37 Specifies the minimum time in minutes after the first stage...

Страница 32: ...If set to 0 the fan will not run after a call for cooling or electric strip heating has been satisfied Comfort Recovery setup step 65 With Comfort Recovery on the thermostat will attempt to reach the...

Страница 33: ...52 Specifies how many degrees below the Cool setpoint the air conditioning will run to satisfy a Cool to Dehumidify demand during unoccupied periods 0 to 20 Reheat Operation With CoolTo Dehumidify Se...

Страница 34: ...settings FDD If FDD is selected when the dry contact is active EQUIPMENT FAULT will appear on the display HOLIDAY If HOLIDAY is selected when the dry contact is active the thermostat will be forced in...

Страница 35: ...use in the subsequent step Average of Wireless Remotes Averages the temperatures of all linked wireless remote sensors AverageThermostat and Wired Remote Averages the temperatures of the wired remote...

Страница 36: ...active when program is in any occupied time Auxiliary Output Programming By Time IfTIME is selected for the Aux Output the following setup steps will appear Aux Output Program Days setup step 58 Speci...

Страница 37: ...emote Temperature is monitored from a wired sensor connected to the Remote Sensor terminals Aux OutputTrigger PointTemp setup step 64 Specifies the temperature from the above selected source above whi...

Страница 38: ...rt settings of the thermostat in order to reduce energy usage on demand This is known as Automated Demand Response ADR You must register to participate in a utility sponsored program if offered by you...

Страница 39: ...to the energy provider s signals It also sets operational parameters for the thermostat The left column of the ADR configuration page allows or prevents access by the utility Here communication with t...

Страница 40: ...Selecting the Overview tab of the ADR page will cause a summary of ADR events to be displayed Installer Setup Automated Demand Response 36...

Страница 41: ...atic Setpoints will set the heat and cool setpoints to the values specified in setup steps 77 and 78 Event Max Cool Setpoint setup step 75 Event Min Heat Setpoint setup step 76 Specifies the range of...

Страница 42: ...t can be automatically raised by 1 to 10 degrees DISPLAY INDICATIONS WHEN AN ADR EVENT IS HAPPENING After setting your desired values for use during an ADR event the scrolling display will give a litt...

Страница 43: ...utton press the WARMER and COOLER buttons together The icon will appear on the display then release the buttons Press all three buttons in the order outlined above for keypad lockout To unlock the key...

Страница 44: ...icons will appear on the display Keep pressing the SETUP button until you see this screen 2 After all the icons appear release SETUP Press and hold FAN for 5 seconds DEFAULTS will appear on the displa...

Страница 45: ...for more detailed instructions Technician Setup contains the following options View the version number of the thermostat View the Dip Switch equipment type settings View the state of the Dry Contact T...

Страница 46: ...t UV Lamp Calendar Days 23 0 720 Days 0 16 Current Humidifier Calendar Days 23 0 720 Days 0 17 Set Service Filter Runtime Hours 22 0 1950 hours 0 18 Set Service Filter Calendar Days 22 0 720 Days 0 19...

Страница 47: ...of wifi sensors currently first linked linked to thermostat This step sensor in only appears if prior step Wireless Remote list 47 Humidity Only With Heat 29 On Off Off 48 Fan With Humidity Demand 29...

Страница 48: ...osed Open 70 Dehumidify only with Cooling 29 On Off On 71 Skyport 30 On Off On 72 Local API 30 On Off Off 73 ADR 37 On Off On 74 ADR Action 37 Observe Setpoint Observe Offset Observe Static Setpoint S...

Страница 49: ...point Limits page 26 SYMPTOM The heating does not attempt to turn on CAUSE The heating setpoint is set too low REMEDY Raise the heating setpoint or raise the heating set point limit See Setpoint Limit...

Страница 50: ...WHATSOEVER ALL WORK UNDERTHETERMS OFTHIS WARRANTY SHALL BE PERFORMED DURING NORMAL WORKING HOURS ALL REPLACEMENT PARTS WHETHER NEW OR REMANUFACTURED ASSUME ASTHEIR WARRANTY PERIOD ONLYTHE REMAININGTIM...

Страница 51: ...ture Adjustment Range Accuracy 10 RH from 30 70 RH 50 90 F Humidity Wire Size Deadband Operating Storage Ambient Conditions Compliance Dimensions Shipping Weight This equipment has been tested and fou...

Страница 52: ...88 1347 rev 3 07 19 Patent Pending...