SIGNAL INDICATORS
The state of the demultiplexer card is signalled with two indicator LEDs.
green:
OPERATION (blinking)
red:
ERROR (blinking)
Error blinking at data errors or loss of communication.
START ADDRESS SWITCHES
The three decimal coding switches set the start address, that is the address of the first channel to be decoded.
The setting is fully decimal, no binary conversion is necessary as is with DIL switches.
S1:
Ones
S2:
Tens
S3:
Hundreds
If the switch block is set to address 000, all outputs are disabled regardless of the data received.
DIP SWITCH SETTINGS
The relay card 3202R may configured to match different applications. Set the DIP-switches 1...4 on the DMX start
address selector board to achieve the desired mode of operation. Settings will be retained in nonvolatile memory
if the adress board is removed after.
S1:
HOLD Mode
With HOLD mode ON, the last valid DMX data will be retained at signal loss. Otherwise, all outputs
will be set according to S2 setting (below).
OFF
HOLD mode off
ON
HOLD mode on
S2:
Safety Level
With HOLD mode OFF, the outputs will be set:
OFF
all outputs set to OFF
ON
all outputs set to ON
S3, S4:
Switching Hysteresis Selection
SETTING
RELAY OFF
RELAY ON
S3=OFF
<45%
>55%
S4=OFF
S3=ON
<25%
>75%
S4=OFF
S3=OFF
<10%
>90%
S4=ON
S3=ON
0%
>0%
S4=ON