Operation
Sorensen SFA Series
CAUTION!
This option is not intended to allow operation of the power supply at
excessive voltages. Refer to Section 2 INSTALLATION for maximum
terminal voltages.
Following are Figure 3–4 with the connector's pin-out diagram, and Table 3–1
with ANALOG CONTROL connector designations and functions:
Figure 3–4. ANALOG CONTROL Connector (J1) Pin-out
Designator
Schematic
Symbol
Electrical
Chars.
Functional Description
1
ISO
ON/OFF
Zin ~ 6 k
Ω
Isolated remote on/off. Externally supplied AC/DC voltage source
for on/off control. A positive (+) 12 to 240 VAC or 6 to 120 VDC
voltage will turn on the supply. This input control is optically isolated
from the power supply circuit up to 500 VDC. See Section 3.5.
2 ISO
RTN
—
Isolated circuit return used with isolated on/off control
J1-1 and J1-14.
3
REM OC
SET
Zin ~
20 k
Ω
Remote overcurrent set. A remote signal sets the overcurrent
trip level. 0-5.5 VDC = 0-110%. Apply a 10.5 VDC to 13.3
VDC signal for 4 seconds to reset an OCP condition. See
Section 3.6.
4 Not
Used
5 ON/OFF
Must sink
~1mA to
enable
Remote on/off. Switch/relay contacts or a direct short
between this terminal and circuit common turns on the unit.
6
COM
†
-
Circuit Common. Same potential as the negative output
terminal.
3-8
M550292-01 Rev C
Содержание SFA Series
Страница 2: ......
Страница 4: ...This page intentionally left blank M550292 01 Rev C ii...
Страница 6: ...This page intentionally left blank M550292 01 Rev C iv...
Страница 8: ...This page intentionally left blank M550292 01 Rev C vi...
Страница 10: ...This page intentionally left blank M550292 01 Rev C viii...
Страница 14: ...This page intentionally left blank iv M550292 01 Rev C...
Страница 41: ...Sorensen SFA Series Operation Figure 3 7 Remote Sensing Operation at the Load M550292 01 Rev C 3 13...
Страница 46: ...Operation Sorensen SFA Series This page intentionally left blank 3 18 M550292 01 Rev C...
Страница 52: ...Verification and Calibration Sorensen SFA Series This page intentionally left blank 4 6 M550292 01 Rev C...
Страница 56: ...Maintenance Sorensen SFA Series This page intentionally left blank 5 4 M550292 01 Rev C...