34
Special functions
menu 7
12
12
12. Special functions
Menu “7. Special functions” is used
to set basic items and expanded
functions.
The menu is closed by pressing
“esc” or selecting “Exit special func-
tions”.
12.1 Program selections
menu 7.1
The suitable hydraulic variant for the speci
fi
c application is selected and
set here (see 2.5 Hydraulic variants). The associated diagram can be
displayed by pressing “info”.
Setting range: 1-6/default setting: 1
Caution
Caution
Normally the program selection is made only once during initial
commissioning by the specialist. Incorrect program selection can
lead to unpredictable errors.
Other than the time all
settings may only be made
by a specialist.
12.3 Sensor calibration
menu 7.3 / 7.3.1 - 7.3.3
Deviations in the temperature values displayed, for example due to cables
which are to long or sensors which are not positioned optimally, can be
compensated for manually here. The settings can be made for each indi-
vidual sensor in steps of 0.5°C.
Offset S1...S3 per setting range: -50°C...+50°C default setting: 0°C
Caution
Settings are only necessary in special cases at the time of initial
commissioning by the specialist. Incorrect measurement values
can lead to unpredictable errors.