3.2 Electrical connection
(continued)
3.2.1 Solar with circulation
Low voltage
max. 12VAC/DC
connection in the left-hand terminal
compartment!
Terminal: Connection
for:
S1
Sensor 1 collector
S2
Sensor 2 storage
S3
Sensor 3 (Thermostat)
S4
Sensor 4 (circulation)
S5
Sensor 5 (opt. circula.)
S6
Sensor 6 (optional,
see 11.5)
+
not used
-
jumper terminal
block-
Connection of sensor earths (S1-S6)
via terminal block sensor-
The polarity of the sensors is freely
selectable.
Sensor side
max. 12V
Danger!
Caution
Mains side
230VAC
Mains voltages
230VAC 50-60Hz
Connection in the right-hand terminal
compartment!
Terminal: Connection
for:
R1
Pump L (speed)
N
Pump N
L
Mains phase conductor L
N
Mains neutral conductor N
R2
Pump L (no speed)
N
Pump N
R3 Thermostat
L
N
Thermostat N
The PE protective conductor must be
connected to the PE metal terminal
block!
Brief description:
Function
∆
T R1 (10.5) switches the
pump at relais R1.
Function Tset S3 (10.7) switches the
additional heating at relais R3.
Function Tset S4 (10.11) switches the
circulationpump at relais R2.
Caution
Relais R1: Only for speed
control of standard pumps,
minimum load 20 VA