19
Various settings can be made depending on the selection of hydraulic variant
1-20. This is explained in more detail in Table 5.17. This table also indicates the
associated reference sensors and switch outputs. The following pages contain
generally valid descriptions for the settings.
Caution
5. -
Settings
The necessary basic settings required for
the control function are made in menu “5.
Settings”.
5.1. -
Tmin Collector
Enable/start temperature at sensor 1
If this value is exceeded at the collector sensor S1 and the other conditions are also
met, then the controller switches on the associated ventilator. If the temperature at the
sensor drops below this value by 5 °C, then the ventilator is switched off again.
Caution
This does not under any circumstances
replace the safety facilities to be
provided by the customer!
The menu is closed by pressing “esc” or select-
ing “Exit settings”.
Settings