Setting Simple Connection of AUX Bus Remote Panel
Pre
par
at
ion
Setting Simple
Connection of AUX Bus
Remote Panel
Connecting the MKS-8080/8082 AUX Bus Remote Panel
to the control panel using an S-Bus data link normally
requires an HKSP-R80 Routing Switcher Controller Board
or similar primary station and various connection settings.
However, using a simple connection, the MKS-8080/8082
can be connected directly without the need for an S-Bus
data link primary station.
A simple connection is possible if the following conditions
are satisfied.
• There are no devices other than the control panel and
MKS-8080/8082 connected on the S-Bus data link.
• There are no more than 16 MKS-8080/8082 units
connected on the S-Bus data link.
For information about the input signals and buses that can
be controlled by the MKS-8080/8082, see
for MVS-6500 system assigned to S-Bus matrix”
(
.
For details about the setting status of the AUX bus remote
panel for a simple connection, refer to the User’s Guide.
For details about the settings on the AUX bus remote
panel, refer to the Operation Manual for the MKS-8080/
8082.
1
Initialize the MKS-8080/8082 settings.
This can be executed on the MKS-8080/8082.
2
Set the MKS-8080/8082 station number.
Set a number in the range 2 to 17.
This can be executed on the MKS-8080/8082.
3
Set the S-Bus data link primary station role to the
control panel.
Set the STATION ID switches on the front of the
board in the MVS-6520/6530 SLOT 8 to 001 (switch
1 only to the OPEN position).
4
Carry out a reset.
Initialize menu
a
Open the Engineering Setup >System >Initialize
menu (7315).
b
Select the control panel “PNL1” in the [Device]
column.
c
In the <Initialize> group, select [Reset].
d
Press [Execute].
e
Check the message, then press [Yes].
This reboots the system, and connection to the
MKS-8080/8082 becomes possible after the system
starts.
5
Set the position of the MVS system in S-Bus space.
Router menu
a
Open the Engineering Setup >Router/Tally
>Router menu (7361).
b
In the <Device> group, select the target device.
In this example, select [SWR1].
Switcher processor
Board
STATION ID switch
MVS-6520/6530
CA-85
S3801
Reset
Device
Execute
Level
Source
Destination
Matrix Size
Device