Instruction for use | Supercal 5 

11. Technical Information

11.1 Calculator Supercal 5 

Temperature Measurement

  Pt500 according to EN 60751 

  2- or 4-wire

  Absolute temperature range

   Approved  range

   Homologation  range

 Response limit

 Temperature resolution t

 Temperature resolution Δt

  Environment class A

– 20°C to 200°C

1°C to 200°C

3 K to 150 K

0,2 K

0,1 K

0.01K

E1/M1

Temperature Measuring Cycle

 Battery operated

   Mains  operated

10 s

3 s

Medium Temperature

 Operation 

 Storing and transport

5°C to 55°C

–20°C to 70°C (dry environment)

Display 

 Illuminated dot-matrix

128 × 64  pixels

Display Units

 Energy 

 Volume

 Additional pulse inputs 

 Temperature

kWh, MWh, MJ, GJ, kBtu, MBtu, Mcal, Gcal

L, m

3

, gal (US), kgal (US) 

Energy or volume

°C, °F

Lifespan Supply Modules

 w/o supply 

 D battery

6 + 1 years (backup for metrological part)

12 + 1 years

Degree of Protection

 IP Code

IP 65 in accordance to IEC 60529

Pulse Inputs

Frequencies 

  Without supply

  D battery

  External Mains

Input voltage

maximum 5 Hz

maximum 200 Hz 

maximum 200 Hz

0 V to 30 V

Pulse Outputs

Frequencies

 

  Without supply

  D battery

  External Mains

Output voltage

maximum 5 Hz 

maximum 200 Hz

maximum 200 Hz

0 VAC to 60 VAC

Optical interface

 Interface

according to IEC 62056-21:2002

NFC Interface

 Interface

according to ISO/IEC 14443 Type A

M-Bus interface

 Interface

 Baud rate

 Galvanic isolation

according to EN 13757-2/3 

300 to 9,600 baud

3.75 kV

Technical Data

Содержание 26277017

Страница 1: ...Instruction for use Supercal 5 I...

Страница 2: ...ernal reproduction in tended for evaluation of the product or its proper use is permitted and not subject to au thorisation Warranty Please contact your local Sontex representative for warranty inform...

Страница 3: ...per Part 15 4 4 2 Calculator Lower Part 15 4 5 Dimensions 16 4 6 Mounting 16 4 6 1 Before Mounting 16 4 6 2 Wall Mounting 17 4 6 3 Top Hat Rail Mounting 18 4 7 Installation Instructions For Temperatur...

Страница 4: ...37 6 11 Service 40 6 12 Sealing 42 6 13 Nowa Unicon 42 6 14 Save Operating Data 42 6 14 1 Data Backup 42 7 Commissioning 44 7 1 Commissioning of the Supercal 5 44 7 1 1 Checking Date and Time 44 7 1...

Страница 5: ...3 Refrigeration Energy Combined Cold Heat Meter 53 11 9 4 Insulation Regulations for Refrigeration Systems 54 11 10 Calibration and Measurement Data 54 11 11 Nowa 54 12 Notes on Project Planning 56 1...

Страница 6: ...6 Instruction for use Supercal 5...

Страница 7: ...ls for Supercal 5 S will be explained as a note in the current man ual s different sections 1 2 Target Groups This documentation is intended for the system operator and the installer of the calculator...

Страница 8: ...CE Warning non observance of which may result in damage to property Reference Information that is important for a specific topic or goal but not relevant to security Documentation Reference to documen...

Страница 9: ...the task requirements Follow the instructions in this document 2 2 Intended Use Supercal 5 is an electronic device for recording energy flows in heating and cooling systems It can be used universally...

Страница 10: ...repair of an electrical electronic de vice Only use original Sontex spare parts and accessories Environmental requirements If the plastic housing of the Supercal 5 is permanently exposed to certain v...

Страница 11: ...lass according to OIML or EN 1434 E1 M1 Protection class according to OIML or EN 1434 IP65 Temperature range 1 200 C Temperature difference 3 150 K Temperature range cooling K 1 200 C Temperature diff...

Страница 12: ...6070 5 Type SC5I S N 26277017 2021 Pulse value installation flowmeter parameters See display M Bus wM Bus 868MHz Sontex SA Rue de la Gare 27 2605 Sonceboz Switzerland NFC Calculator Heating Cooling 1...

Страница 13: ...9 4 2016 or 2014 32 EU L 96 149 from 20 4 2016 Meas urement Instruments Directive MID as well as OIML R75 and EN 1434 If the calculator with temperature sensors is to be used in business the flow sens...

Страница 14: ...nditions must be respected Exact specifications can be found in the chapter Technical Information Observe the following points For storage and transport the device must be packed shockproof The origin...

Страница 15: ...us LED 5 Two operating buttons 6 Optical interface 7 NFC Interface 8 External mains battery supply 9 Connection terminal block 10 Rubber gommets IP65 11 Strain reliefs for connection cable and earthin...

Страница 16: ...vibrations in the piping system the calculator should be mounted separately on the wall For medium temperatures above 90 C the calculator should be mounted separately The flow sensor should be mounte...

Страница 17: ...ning regulations must be observed The readability of the calculator and all nameplates must be observed The complete heat meter consists of the following three subunits Flow sensor Calculator Supercal...

Страница 18: ...erference If there is a danger of electrical or electromagnetic interference temperature sensors in 2 and 4 wire technology with shielded cables or shielded cables at the connection heads must be used...

Страница 19: ...ithout delays and heat dissipation errors In pipelines up to DN 150 the temperature sensors are installed directly or employing ther mowell The dynamic measuring range of the sensor tip is located as...

Страница 20: ...nection cable must have four wires the wire cross section should be at least 0 5 mm2 The insulation of the temperature sensor cables can be made of PVC or silicone Sontex recommends the use of silicon...

Страница 21: ...he installation points must be sealed last 4 8 Installation Check For the installation of the heat meter and the associated temperature sensors the general installation regulations according to EN 143...

Страница 22: ...f the calculator and also the identification plates must be followed The flow sensor should be mounted BEFORE any control valve to exclude any potential parasitic influences During commissioning the p...

Страница 23: ...ut additional pulse input 1 52 pulse input additional pulse input 2 53 pulse input additional pulse input 2 Outputs 16 open collector output 1 Energy volume or tariff counter 17 open collector outputs...

Страница 24: ...nput Terminal 10 flow meter 440 white cable Terminal 11 flow meter 440 green cable Power supply flow sensor Terminal 9 3 7V 3 0V max 1mA the flow sensor 440 brown cable Input frequency normal mode Max...

Страница 25: ...or fast mode can be set up by software Technical Characteristics of the Two Pulse Inputs Designation Description 2 inputs A1 at terminals 50 51 A2 at terminals 52 53 Input frequency normal mode Max 5...

Страница 26: ...near or scaled pulses Maximum electrical pulse frequency 200 Hz 20 5 6 1 1 Technical Characteristics of the Two Open Collector Pulse Outputs Output SC5 Vout Iout Additional counter 0V Counter 2 Counte...

Страница 27: ...ation reset the factory settings are set in accordance with the EN 1434 standard 187 ms 4 6 187ms 1 256 bytes M Bus Command M Bus Answer M Bus Answer Total exchange with 2 retries 1 256 bytes 13 138 m...

Страница 28: ...current consumption values 60 default monthly energy values 5 9 Supercal 5 S Flowmeter included consideration Generally the shielded cables must be grounded with a strain relief Grounding It has to be...

Страница 29: ...ically switches back to the main menu 6 3 Control Buttons The control key can be used to select and confirm the various menus parameters or other selection options within the display Right Key The Rig...

Страница 30: ...lue of the error message parameter in the Service menu 6 5 Commissioning Once the Supercal 5 is unsealed there is an available Commissioning Menu inside the Main Menu This kind of setup menu allows th...

Страница 31: ...enu Errors CumulatedEnergy Cumulatedvolume CumulatedEnergy Tarif1 Cumulated volumetarif 1 Cumulated Energy Tarif2 Cumulated volumetarif 2 Metrological Con guration Service Set day 2 Date Power Volume...

Страница 32: ...th Super prog Windows 1 Cumulated Input value 3 Cumulated Input value 4 Main Menu also shows the cumulated cooling energy and the cumulated cooling volume for combined heating cooling meters ERROR err...

Страница 33: ...Input value 6 1 Temperature high Temperature low Temperature difference 1 Thermal power Flow 1 Set day 1 date Energy accumuleted to the specific date Total debit 1 Set day 2 date Energy accumuleted to...

Страница 34: ...s the selector up a short press switches the selector down A two second press on the right button confirms the selection and opens the selected menu 6 8 Metrological Setup Main Menu Metrological Mount...

Страница 35: ...lue Active only for Supercal 5 S 1 Accuracy class DN nominal diameter Active only for Supercal 5 S 1 PN nominal pressure PS upper limit pressure Active only for Supercal 5 S 1 qp permanent flow rate q...

Страница 36: ...ith five more significant digits 1 Cumulated volume tariff 0 with five more significant digits A long press on the right button does not have any function in Metrological Setup A long press on the lef...

Страница 37: ...lseFactor OUT5 PulseFactor OUT6 Multiplier OUT2 Multiplier OUT3 Pulse Factor OUT2 Pulse Factor OUT3 Multiplier OUT5 Pulse Factor OUT5 Multiplier OUT4 Pulse Factor OUT4 Multiplier OUT6 Pulse Factor OUT...

Страница 38: ...value IN2 Active only when digital input module is in slot 1 This menu must be activated with Superprog Windows 1 Unit electrical pulse IN3 Electrical pulse value IN3 Active only when digital input mo...

Страница 39: ...dows 1 Unit electrical pulse IN6 Electrical pulsee IN6 1 Pulse unit OUT1 Multiplier OUT1 for number of pulses 1 Pulse unit OUT2 Multiplier OUT2 for number of pulses Active only when digital output mod...

Страница 40: ...al ouput module is in slot 2 This menu must be activated with Superprog Windows 1 Pulse unit OUT5 Multiplier OUT5 for number of pulses Active only when digital output module is in slot 2 This menu mus...

Страница 41: ...uttons opens Default Menu 1 Fabrication number 1 Firmware version Firmware CRC32 Firmware version and CRC32 may be dif ferent for future firmware versions 1 Running hours Running Years Days 1 Display...

Страница 42: ...he installer can modify any other meteorological parameter with Superprog Android and Superprog Windows at any time From this moment on if it s required at any given time to come back to the commissio...

Страница 43: ...ronization Daily synchronized ba y 00 00 Monthly synchronized any day The frequency for peak maximal recorded values must be larger and multiple of average time recording frequency The values that can...

Страница 44: ...l correspond to the expected system data The high temperature should be greater than the low temperature and the temperature differ ence should be positive 7 2 Uses 7 2 1 Flow Calculation The paramete...

Страница 45: ...om your local Sontex representative 7 3 1 1 Solar and Refrigeration Systems The Supercal 5 initially calibrated for water ensures precise measurement even with glycol mix tures Here the medium to be m...

Страница 46: ...leaned with a dry soft cloth For service requests please have the serial number of the device and the error number ready Please always state the error number and the Service menu s information identif...

Страница 47: ...but its value can not be read out Cross the probes if Err1 appears afterwards probe 1 is defective or it is not the correct type 16 Range Sensor 1 Temperature sensor 1 min Range error Check the ral v...

Страница 48: ...our Return of Goods Form as described in Chapter 14 Return of goods form see also www sontex ch downloads To preserve and protect the environment and reduce waste of natural resources and pollution th...

Страница 49: ...olume Additional pulse inputs Temperature kWh MWh MJ GJ kBtu MBtu Mcal Gcal L m3 gal US kgal US Energy or volume C F Lifespan Supply Modules w o supply D battery 6 1 years backup for metrological part...

Страница 50: ...tage 3 6 VDC Nominal capacity min 4 1 Ah Maximum ambient temperature 55 C 11 2 3 Estimating the Battery Life of an M Bus Application The battery life of Supercal 5 doesn t depends on any of these para...

Страница 51: ...c Installation situation Accuracy requirements for the flow sensor Available inlet outlet distances measuring accuracy Price performance ratio in general In order to achieve the highest possible resol...

Страница 52: ...re The formula applies accordingly 11 8 Temperature Measurement 11 8 1 General Information The basic measuring range of the calculator is 20 C to 200 C Approved according to MID the measuring range is...

Страница 53: ...e subassemblies If the calculator and temperature sensor are tested as a unit it is 2 K according to PTB ap proval and 3 K according to MID approval No approvals below 3 K are provided for the EC type...

Страница 54: ...ey are determined in the factory or by an authorized authority They are consequently protected against unauthorized intervention by calibration seals If these calibration relevant safety symbols are d...

Страница 55: ...55 Instruction for use Supercal 5 The interfaces of the NOWA adapter...

Страница 56: ...roject Planning 12 1 Safety and Security The Supercal 5 calculator is produced in accordance with the state of the art and complies with EN1434 and is reliable in operation If the calculator is operat...

Страница 57: ...has been completed 12 9 Service and Repairs Service and repair work may only be carried out by qualified personnel who have been ex pressly authorized to do so by Sontex The calculator must generally...

Страница 58: ...flow saturation the flow measurement stagnates at 2 4 nominal flow but the volume is still cumulated In this case the red led will light on and an error message event will be recorded The cut off fun...

Страница 59: ...50 DN125 100 10 000 2 000 1 000 0 600 240 000 300 DN150 150 15 000 3 000 1 500 0 900 360 000 350 DN200 250 25 000 5 000 2 500 1 500 600 000 450 DN250 400 40 000 8 000 4 000 2 400 960 000 Length mm Con...

Страница 60: ...9 190 1 5 m3 h 16 25 125 79 110 1 5 m3 h 1 16 25 125 79 190 2 5 m3 h 1 16 25 125 79 190 3 5 m3 h 1 16 25 2 78 105 260 3 5 m3 h 25 16 25 3 115 134 260 85 4 M 12 6 m3 h 1 16 25 2 78 105 260 6 m3 h 25 16...

Страница 61: ...m3 h 125 16 250 250 254 210 8 M 16 100 m3 h 125 25 250 270 270 220 8 M 24 150 m3 h 150 16 300 285 286 240 8 M 20 150 m3 h 150 25 300 300 300 250 8 M 24 150 m3 h 150 16 500 285 286 240 8 M 20 150 m3 h...

Страница 62: ...250 125 11 2 51 8 0 25 40 80 225 SS 16 25 80 800 400 14 4 142 0 09 40 80 300 SS CI 16 25 80 800 400 13 1 142 0 09 60 100 250 SS 16 25 120 1 200 600 NA 210 0 10 60 100 360 SS CI 16 25 120 1 200 600 19...

Страница 63: ...ter pipe Automatic module recognition Once the modules have been installed they are automatically detected by the Supercal 5 I within 30 seconds Designation Articles Slot 1 Slot 2 Needs mains power su...

Страница 64: ...en pdf Sontex SA 2605 Sonceboz Switzerland Tel 41 32 488 30 00 Email sontex sontex ch www sontex ch Products return form Customer E Mail Reference Date Returned products Reason for return Warranty Re...

Страница 65: ...orth America Canada USA Africa South Africa Status 11 2018 subject to changes Further information can be found on our website www sontex ch contact 16 Declaration of Conformity Sontex hereby declares...

Страница 66: ...Sontex SA Rue de la Gare 27 CH 2605 Sonceboz Tel 41 32 488 30 00 sontex sontex ch www sontex ch 21 03...

Отзывы: