Decommissioning | 12
KD-557 | 1000241 | EN | 02
83 / 100
12.2 Switching the storage system off to electrically isolate it
DANGER
High battery voltage (> 200 V)
Danger to life due to electrocution!
When battery cables are connected, the central unit always carries the voltage
of the battery modules, even if the storage system and mains voltage are
switched off.
To disconnect the battery voltage from the central unit:
Unplug the battery cables from
all
battery modules.
Before
working on the storage system
it must be completely switched off to be electrically
isolated.
1.
Press the ON/OFF switch. The sonnen Eclipse switches off.
2. Switch off the grid voltage using the miniature circuit breaker for the mains line.
3. Take steps to ensure that these switches cannot be switched on again.
4. Wait at least five minutes until the internally stored energy in the inverter has fully dis-
charged.