6 | Connecting the storage system
40 / 100
Installation instructions sonnenBatterie 10
6.4.3 Connecting the Modbus cable
NOTICE
Communication lines too long
Ensure that the Modbus line and Ethernet line connected to the storage
system do not exceed a maximum length of
150 m
.
• Measurement data is transmitted from the power meter to the storage system using the
Modbus line.
• The Modbus line is connected to the power meter and the central unit of the storage
system.
It is essential to ensure that a screened patch cable is used and that the screen
of the Modbus line is earthed in order to ensure optimal data transmission.
Use a patch cable with the following properties as the Modbus cable:
• The patch cable is Cat 6.
• The patch cable is shielded.
Earth the screen of the Modbus line for the power meter
6
.
Connect the patch cable to the central unit of the storage system (
MOD [Meter]
).
Use the fixing ties from the accessories set to affix the attached cable to the power
module.
Connect the other end of the patch cable to the power meter as shown in the figure.
If there is no jumper on the Modbus terminal strip between pins 6 and 8:
Install a jumper between pins 6 and 8 on the Modbus terminal strip.
6
Install the supplied screen clamp for this purpose as described in the provided instructions.