31
17. Reinstall access panel
Fig. 61 Reinstall access panel
18. Verify protected load panel isolation
Damages caused by improper
wiring are not covered by your
warranty.
▶
Ensure the storage system's breaker in
the main distribution panel is in the open
position.
▶
Ensure there is no voltage present on the
storage system's Micro-grid terminals and in
the Protected Load Panel.
These measurements should read 0V. If voltage
is present at any location in the Protected Load
Panel or on the storage system's micro-grid
terminals, you must correct the problem before
turning on the unit.
19. Reinstall dead front panel
0
Fig. 62 Re-install dead front panel
20. Begin the commissioning process