MRU-30
– USER MANUAL
26
4.8 Measurement of resistance of protective conductors and equipo-
tential bonding (R
CONT
)
Note:
The measurement complies with the requirements specified in the standard:
EN 61557-4 (V<24V, I>200mA and
R≤10Ω).
Use
<<
or
>>
buttons to select the
measurement mode:
R
CONT 200mA
.
The LED
is illuminated. The meter is now in the state of
measuring interfering noise voltage between the
measurement terminals.
The meter is ready for
measurement.
Press
START
to begin measurement.
Connect the test leads according to this diagram:
Содержание MRU-30
Страница 1: ......
Страница 2: ...MRU 30 USER MANUAL 2 ...
Страница 54: ...MRU 30 USER MANUAL 52 NOTES ...
Страница 55: ......
Страница 56: ...MRU 30 USER MANUAL 54 ...