MRU-30
– USER MANUAL
12
Use the
<<
or
>>
buttons to select the
measurement mode:
3P.
The LED
is
illuminated. The meter is now in the state of
measuring the interfering noise voltage
seen on the measurement terminals.
Press the
SET/SEL
button
to select the
measurement voltage.
Use the
and
button to set the meas-
urement voltage value to 25 V or 50 V.
or
Press
ENTER
to save the setting or
press
ESC
to exit without saving.
Drive the current electrode into the ground and connect it to the
H
terminal of the
meter.
Drive the voltage electrode into the ground and connect it to the
S
terminal of the
meter.
Connect the earth electrode object of test to the
E
terminal of the meter.
All 3 electrodes should be aligned in a straight line.
The meter is ready for
measurement.
Connect the test leads according to this diagram: