CONNECTIONS
Make the connections
of the installation before
connecting the power.
230 V~ 50 Hz max. 2 VA
INPUT POWER
INPUTS
CALORIMETER
The relay contacts are potential-free because they operate
as switches.
The application must be powered externally.
NO
C
(230 Vac)
N
L
Probe 1
Probe 2
Probe 3
Probe 4
+10%
- 15%
OUTPUTS
5A 250 V~ relays
R1
CONTROL KEYS
Up arrow
to move to another
menu or sub-menu.
ESC key
to cancel, exit or finish
without saving.
OK key
to confirm data and
settings.
Down arrow
to move to another
menu or sub-menu.
FLANGE FOR
INSTALLATION ON DIN RAIL
7 PT1000 probes
Range: -50 ºC to +200 ºC
Before making any electrical connections it is advisable to carefully read the whole manual and ensure
compliance with the technical requirements for correct operation of the installation.
Probe 5
Probe 6
Probe 7
Cal. / GND
NO
C
R2
NO
C
R3
NO
C
R4
NO
C
R5
NO
C
R6
ESC
OK
576
Sonder
S
E
T
%
SCREEN
INSTALLATION AND CONNECTION
7
SETTINGS
For normal use of your installation the factory settings are considered to be the most common for each type of
system. If they are of use to you, the device is ready to control and regulate your installation. If, due to the needs
of your installation, you require other settings, read this section carefully.
In the menu you can adjust the parameters that define how the installation will operate.
default values and setting ranges
SETTING
RANGE
ADJUSTED
Adjustment mode
Activation differential
Deactivation differential
Tank temperature alarm *
Temperature differential
Minimum setting limit
Maximum setting limit
Minimum ambient limit
Maximum ambient limit
Probe calibration
Priority in the accumulator *
Accumulator cooling (1…6):
Sequential priority
Display light
Password
Winter / Summer
4.0 to 20.0 ºC
1.0 to 4.0 ºC
5 to 130 ºC
0.3 to 9.0 ºC
5 to 80 ºC
90 to 130 ºC
6 to 17 ºC
18 to 30 ºC
-10.0 to +10.0 ºC
5 to 130 ºC
5 to 130 ºC
ON/OFF
ON/OFF
OFF (0) / ON (1...9999)
Winter
6.0 ºC
2.0 ºC
85 ºC
2.0 ºC
10 ºC
90 ºC
6 ºC
30 ºC
0.0 ºC
5 ºC
130 ºC
OFF
OFF
OFF
* The values of the
tank alarm
and
accumulator priority
settings are interrelated in such a way that the alarm
cannot be set below the value of the tank priority and the tank priority value cannot be set above that of the
alarm, since this can block the setting adjustment range.