background image

CONNECTIONS

Make the connections

of the installation before 

connecting the power.

230 V~       50 Hz   max. 2 VA

INPUT POWER

INPUTS

 

CALORIMETER

The relay contacts are potential-free because they operate 
as switches.
The application must be powered externally.

NO

 C

(230 Vac)

N

L

Probe 1

Probe 2

Probe 3

Probe 4

+10%
 - 15%

 OUTPUTS  

5A   250 V~  relays

 R1

CONTROL KEYS

Up arrow

to move to another 
menu or sub-menu.

ESC key

to cancel, exit or finish 
without saving.

OK key

to confirm data and 
settings.

Down arrow

to move to another 
menu or sub-menu.

FLANGE FOR 

INSTALLATION ON DIN RAIL

7 PT1000 probes
Range: -50 ºC to +200 ºC

Before  making  any  electrical  connections  it  is  advisable  to  carefully  read  the  whole  manual  and  ensure 
compliance with the technical requirements for correct operation of the installation.

Probe 5

Probe 6

Probe 7

Cal. / GND

NO

 C

 R2

NO

 C

 R3

NO

 C

 R4

NO

 C

 R5

NO

 C

 R6

ESC

OK

576

Sonder

S

E
T

%

SCREEN

INSTALLATION AND CONNECTION

7

SETTINGS

For normal use of your installation the factory settings are considered to be the most common for each type of 
system. If they are of use to you, the device is ready to control and regulate your installation. If, due to the needs 
of your installation, you require other settings, read this section carefully.

In the menu you can adjust the parameters that define how the installation will operate.

default values and setting ranges

SETTING

RANGE

ADJUSTED

Adjustment mode

Activation differential

Deactivation differential

Tank temperature alarm *

Temperature differential

Minimum setting limit

Maximum setting limit

Minimum ambient limit

Maximum ambient limit

Probe calibration

Priority in the accumulator *

Accumulator cooling (1…6):

Sequential priority

Display light

Password

Winter / Summer

4.0 to 20.0 ºC

1.0 to 4.0 ºC

5 to 130 ºC

0.3 to 9.0 ºC

5 to 80 ºC

90 to 130 ºC

6 to 17 ºC

18 to 30 ºC

-10.0 to +10.0 ºC

5 to 130 ºC

5 to 130 ºC

ON/OFF

ON/OFF

OFF (0) / ON (1...9999)

Winter

6.0 ºC

2.0 ºC

85 ºC

2.0 ºC

10 ºC

90 ºC

6 ºC 

30 ºC

0.0 ºC

5 ºC 

130 ºC

OFF

OFF

OFF

* The values of the 

tank alarm

 and 

accumulator priority

 settings are interrelated in such a way that the alarm 

cannot be set below the value of the tank priority and the tank priority value cannot be set above that of the 
alarm, since this can block the setting adjustment range.

30

MENU

Содержание Allegro 576 BOX

Страница 1: ... Manual Energy control Avenida la Llana Nº 93 P I La Llana 08191 RUBÍ Barcelona Spain Tel 34 93 588 42 11 Fax 34 93 588 49 94 www sonder es info sonder regulacion com SONDER REGULACIÓN S A Allegro 576 RAIL code 20 043 Allegro 576 BOX code 20 054 ...

Страница 2: ...5815VØ MAY 09 2 35 NOTES ...

Страница 3: ...scription Technical specifications Dimensions Connections Operation Getting started Probe and relay test Screen view Configuration Factory settings and resetting Resource control Menu Statistics Functions Systems Settings 33 4 5 6 6 6 6 7 8 8 9 10 11 12 13 16 16 18 22 26 ...

Страница 4: ...modify the product technical data and assembly and use instructions without prior notification WARRANTY CONDITIONS This device has Three year warranty The warranty is limited to the replacement of faulty parts which will be restored to the same condition in which they were received No packaging batteries instructions or any other accessories included with the product will be replaced We cannot acc...

Страница 5: ...3 channels 3 alarms Telephone control landline mobile 1 channel 1 alarm Water meter with pulse output L 50mm L 100mm L 200mm Conductive paste for sheaths 5 PRESENTATION Stainless steel sheaths GSM Consult us about models for remote management and data storage with SD card Visit our WEBSITE New products All our products Technical documentation Catalogues www sonder es Consult our wide range of prod...

Страница 6: ... has reached 45 the swimming pool is heated to dissipate the excess heat instead of accumulating it in the collectors thus preventing the installation from overheating Example with system 6 2 Accumulator priority ºC AC 1 AC 2 AC 3 65 40 5 H W U H Swimming pool In summer Tank alarm ºC AL 1 AL 2 AL 3 70 45 35 Since the underfloor heating does not need to be activated during the summer its priority c...

Страница 7: ...each type of system If they are of use to you the device is ready to control and regulate your installation If due to the needs of your installation you require other settings read this section carefully In the menu you can adjust the parameters that define how the installation will operate default values and setting ranges SETTING RANGE ADJUSTED Adjustment mode Activation differential Deactivatio...

Страница 8: ...lthough only 1 symbol is shown on the screen All the settings are preset to factory default values If these values do not suit the needs of your installation consult page 26 to configure them 8 OPERATION ESC OK 576 Sonder Accumulator cooling This parameter allows you to reduce the temperature of the accumulator by recirculating the collector when it detects that the collector temperature is lower ...

Страница 9: ...key the system returns to normal operation and the relays return to the status required by the system at that time With the password OFF The system does not exit the test menu until the ESC key is pressed forced manual mode Then move on to the relays forced manual where you can manually activate deactivate each relay Press OK to activate deactivate relay R1 Press to move on to the next relay Press...

Страница 10: ...LIGHT TIMER LIGHT parameter OFF 10 ESC OK 576 Sonder This screen informs you that The probe assigned to the radiator has a reading error S S OPERATION SETTINGS 27 Tank temperature alarm This parameter defines a temperature alarm for each accumulator depending on the system a unit heater or cooling system is activated another accumulator is charged or circulation is stopped In the PARÁMETROS menu p...

Страница 11: ...to move to PARÁMETROS and then press OK In the menu you can adjust the settings that will define the operation of the installation Winter or summer mode Activation differential Deactivation differential Temperature alarm in tanks 1 to 6 Temperature differential general for all settings Minimum setting limit Maximum setting limit Minimum ambient limit Maximum ambient limit Separate calibration for ...

Страница 12: ...limit Maximum setting limit Active system 1 1 1 tank 1 pump If the password is activated it is impossible to reset the values and restore the factory settings To do so it is necessary first to deactivate the password value 0 in the settings menu If an unauthorised user tries to reset the values he would press the ESC key for 10 seconds and only be able to enter the probe and relay test When you ex...

Страница 13: ...3 3 1 3 2 3 3 5 1 5 2 5 3 6 1 6 2 6 3 4 1 X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X 13 OPERATION Hot water S4 S5 R3 S3 R5 R2 S1 S7 R6 A B C D EXCHANGER PURIFIER F R1 R4 S6 E S1 S2 S3 S4 S5 S6 S7 R1 ...

Страница 14: ... S S S S S OK S S S S S S S S S S S S S S S S ESC S S S S S S S S S S OPERATION collector array 2 pumps 2 tanks collector array tank swimming pool 2 pumps collector array tank heating 2 pumps collector array 2 tanks pump 3 way valve collector array tank swimming pool pump 3 way valve collector array tank heating return pump 3 way valve 2 collector arrays east and west 2 tanks 2 pumps 3 way valve 2...

Страница 15: ...n Use the keys to move on to the next system To confirm the chosen system press OK and press the ESC key to return the previous menu Once the system has been configured the unit saves the changes and returns to normal operation SYSTEMS The representation of the units on these diagrams is symbolic One solar panel means there is one array of solar collectors but when there are 2 it means that there ...

Страница 16: ...e solar system you need for your installation and then the functions since you may not be able to configure the rest of the functions according to relays the systems leaves frees MENU Thermostat 1 2 3 independent Thermostat 1 2 ambient Anti frost Double pump alternation Cooling by unit heater Calorimeter Tubular sensor Return increase OR AND Regulates the temperature of a probe heating underfloor ...

Страница 17: ...s ESC to return to the FUNCIONES menu This function conditions the status of a relay based on the status of all the selected relays For example if you choose R1 as the slave relay and R2 R4 and R6 as the main relays R1 will be activated when R2 AND R4 AND R6 are activated When any one of the main relays is off the slave relay switches off AND ESC OK 576 FUNCTIONS 20 Press OK to enter the function ...

Страница 18: ...to enter the function settings where you can activate deactivate the function and set the total time that each pump will operate before changing 4 to 120 hours Press to change the flashing value and press OK to confirm the selection Press ESC to return to the FUNCIONES menu S S This function allows you to double a pump in your installation so that the two pumps work in alternation Double pump alte...

Отзывы: