CONFIGURATION
Once all the connections have been made and
the device is connected to the mains, the device
shows the screen operating in normal mode with the
factory settings (page 12).
Press both keys together for 5 seconds
to show the main menu on the screen. Here you can
use the keys to choose a sub-menu.
Press
OK
to enter the chosen sub-menu, such as
Functions.
Press the keys to move around the sub-
menu until you find the function you want to configure.
These screens indicate the status of the function.
Press
OK
in the desired function to configure the
values (the value to be changed flashes). When
you have changed the value, press
OK
to
save and move on to the next value. When all the
values for this function have been changed, save the
changes and return to the sub-menu.
Press
ESC
to return to the functions sub-menu
without saving the changes.
Press
ESC
again to return to the main menu.
Press
ESC
again to return to normal regulation
operation and after 15 minutes without touching any
keys the screen light will switch off. Press any key to
return to normal mode.
This method is applicable to all configuration
menus and sub-menus.
11
ESC
OK
576
Sonder
ESC
OK
576
Sonder
ESC
OK
576
Sonder
ESC
OK
576
Sonder
ESC
OK
576
Sonder
OPERATION
S S
S S
S S
S S
For normal use of your installation the factory settings are considered to be the most common for each type of system. If they
are of use to you, the device is ready to control and regulate your installation. If, due to the needs of your installation, you require
other settings, read this section carefully.
To access the menu from normal operation mode, press any key (except
ESC
), use the arrows to move to
PARÁMETROS
, and
then press
OK
.
In the menu you can adjust the settings that will define the operation of the installation.
Winter or summer mode
Activation differential
Deactivation differential
Temperature alarm in tanks 1 to 6
Temperature differential (general for all settings)
Minimum setting limit
Maximum setting limit
Minimum ambient limit
Maximum ambient limit
Separate calibration for each probe (T1 to T7)
Priority of tanks 1 to 6
Cooling of accumulators 1 to 6
Sequential priority
Display light
Password (programming protection)
Summer / Winter mode
This parameter allows you to choose between two different settings for tank
priorities and alarms without having to change them one by one.
- In the
PARÁMETROS
menu press until the
MODE
screen appears.
- Press
OK
to enter the function settings, and use to define the
desired value.
- Press
ESC
to go back and press
OK
to save the adjusted values.
Range: SUMMER or WINTER / Default: WINTER
ESC
OK
576
Sonder
Activation differential
This parameter defines the temperature difference required between the
accumulator and the solar collector for the pump to activate.
- In the
PARÁMETROS
menu press until the
DIF ACTIVACIÓN
screen appears.
- Press
OK
to enter the function settings, and use to define the
desired value.
- Press
ESC
to go back and press
OK
to save the adjusted values.
Range: 4.0 ºC to 20.0 ºC / Default: 6.0 ºC
S S
ESC
OK
576
Sonder
Deactivation differential
This parameter defines the temperature difference required between the
accumulator and the solar collector for the pump to deactivate.
- In the
PARÁMETRO
S menu press until the
DIF DESACTIVACIÓN
screen appears.
- Press
OK
to enter the function settings, and use to define the
desired value.
- Press
ESC
to go back and press
OK
to save the adjusted values.
Range: 1.0 ºC to 4.0 ºC / Default: 2.0 ºC