                SC7202B    Us er Ma nual                   

http://www.sonbus.com/ 

Sha nghai Son

best Industrial Co., Ltd                                                                             Page3

 

converted to a decimal value of 121. If the data magnification is 100, the actual value is 121/100=1.21. 

Others and so on. 

        2. Data Address Table 

Address 

Start Address 

Description 

Data type 

Value range 

40001 

00 00 

temperature 

Read Only 

0~65535 

40101 

00 64 

model code 

read/write 

0~65535 

40102 

00 65 

total points 

read/write 

1~20 

40103 

00 66 

Device ID 

read/write 

1~249 

40104 

00 67 

baud rate 

read/write 

0~6 

40105 

00 68 

mode 

read/write 

1~4 

40106 

00 69 

protocol 

read/write 

1~10 

        3 read and modify device address 
        (1) Read or query device address 

        If you don't know the current device address and there is only one device on the bus, you can use the 

command FA 03 00 64 00 02 90 5F Query device address. 

Device ID 

Function id 

Start Address 

Data Length 

CRC16 

FA 

03 

00 64 

00 02 

90 5F 

        FA is 250 for the general address. When you don't know the address, you can use 250 to get the real 
device address, 00 64 is the device model register. 

        For the correct query command, the device will respond, for example the response data is: 01 03 02 

07 12 3A 79, the format of which is as shown in the following table:  

Device ID 

Function id 

Start Address 

Model Code 

CRC16 

01 

  03 

02 

55 3C 00 01 

3A 79 

        Response should be in the data, the first byte 01 indicates that th e real address of the current device is, 

55 3C converted to decimal 20182 indicates that the current device main model is 21820, the last two bytes 

00 01 Indicates that the device has a status quantity. 

        (2)Change device address 

        For example, if the current device address is 1, we want to change to 02, the command is:01 06 00 66 
00 02 E8 14 . 

Device ID 

Function id 

Start Address 

Destination 

CRC16 

01 

06 

00 66 

00 02 

E8 14 

        After the change is successful, the device will return information: 02 06 00 66 00  02 E8 27 , its format 

is parsed as shown in the following table: 

Device ID 

Function id 

Start Address 

Destination 

CRC16 

01 

  06 

00 66 

00 02 

E8 27 

        Response should be in the data, after the modification is successful, the first byte is the new device 

address. After the general device address is changed, it will take effect immediately. At this time, the user 

needs to change the query command of the software at the same time.   

        4 Read and Modify Baud Rate 
        (1) Read baud rate 

        The device default factory baud rate is 9600. If you need to change it, you can change it according to 

the following table and the corresponding communication protocol. For example, read the current device's 

baud rate ID, the command is:01 03 00 67 00 01 35 D5 , its format is parsed as follows.  

Device ID 

Function id 

Start Address 

Data Length 

CRC16 

Содержание SC7202B

Страница 1: ... 10 SC7202B using the standard RS485 bus MODBUS RTU protocol easy access to PLC DCS and other instruments or systems for monitoring temperature state quantities The internal use of high precision sensing core and related devices to ensure high reliability and excellent long term stability can be customized RS232 RS485 CAN 4 20mA DC0 5V 10V ZIGBEE Lora WIFI GPRS and other output methods ...

Страница 2: ...ect the cable to confirm the correctness and then use it again ID Core color Identification Note 1 Red V Power 2 Green V Power 3 Yellow A RS485 A 4 Blue B RS485 B In the case of broken wires wire the wires as shown in the figure If the product itself has no leads the core color is for reference Communication Protocol The product uses RS485 MODBUS RTU standard protocol format all operation or reply...

Страница 3: ...Code CRC16 01 03 02 55 3C 00 01 3A 79 Response should be in the data the first byte 01 indicates that the real address of the current device is 55 3C converted to decimal 20182 indicates that the current device main model is 21820 the last two bytes 00 01 Indicates that the device has a status quantity 2 Change device address For example if the current device address is 1 we want to change to 02 t...

Страница 4: ...ay value is too small we can correct it by adding 100 The command is 01 03 00 6B 00 01 F5 D6 In the command 100 is hex 0x64 If you need to reduce you can set a negative value such as 100 corresponding to the hexadecimal value of FF 9C which is calculated as 100 65535 65435 and then converted to hexadecimal to 0x FF 9C The correction value starts from 00 6B We take the first parameter as an example...

Страница 5: ...mpany makes no warranties express or implied regarding the sale and use of this product including the suitability for the specific use of the product the marketability or the infringement liability for any patent copyright or other intellectual property rights etc Product specifications and product descriptions may be modified at any time without notice Contact Us Company Shanghai Sonbest Industri...