        Read the baud rate encoding of the current device. Baud rate encoding: 1 is 2400; 2 is 4800; 3 is 9600; 

4 is 19200; 5 is 38400; 6 is 115200. 

        For the correct query command, the device will respond, for example the response data is: 01 03 02 

00 03 F8 45, the format of which is as shown in the following table: 

Device ID 

Function id 

Data Length 

Rate ID 

CRC16 

01 

  03 

02 

00 03 

F8 45 

        coded according to baud rate, 03 is 9600, ie the current device has a baud rate of 9600.  

        (2)Change the baud rate 

        For example, changing the baud rate from 9600 to 38400, ie changing the code from 3 to 5, the 
command is: 01 06 00 67 00 05 F8 1601 03 00 66 00 01 64 15 .  

Device ID 

Function id 

Start Address 

Target Baud Rate 

CRC16 

01 

03 

00 66 

00 01 

64 15 

        Change the baud rate from 9600 to 38400, changing the code from 3 to 5. The new baud rate will take 

effect immediately, at which point the device will lose its response and the baud rate of the device should 
be queried accordingly. Modified. 

        5 Read Correction Value 
        (1) Read Correction Value 

        When there is an error between the data and the reference standard, we can reduce the display error 

by adjusting the correction value. The correction difference can be modified to be plus or minus 1000, t hat 
is, the value range is 0-1000 or 64535 -65535. For example, when the display value is too small, we can 

correct it by adding 100. The command is: 01 03 00 6B 00 01 F5 D6 . In the command 100 is hex 0x64 If 

you need to reduce, you can set a negative value, such as -100, corresponding to the hexadecimal value of 

FF 9C, which is calculated as 100-65535=65435, and then converted to hexadecimal to 0x FF 9C. The 

correction value starts from 00 6B. We take the first parameter as an example. The correction valu e is read 
and modified in the same way for multiple parameters. 

Device ID 

Function id 

Start Address 

Data Length 

CRC16 

01 

03 

00 6B 

00 01 

F5 D6 

        For the correct query command, the device will respond, for example the response data is: 01 03 02 

00 64 B9 AF, the format of which is as shown in the following table: 

Device ID 

Function id 

Data Length 

Data value 

CRC16 

01 

  03 

02 

00 64 

B9 AF 

        In the response data, the first byte 01 indicates the real address of the current device, and 00 6B is the 

first state quantity correction value register. If the device has multiple parameters, other parameters 

operate in this way. The same, the general temperature, humidity have this parameter, the light generally 
does not have this item. 

        (2)Change correction value 

        For example, the current state quantity is too small, we want to add 1 to its true value, and the current 

value plus 100 correction operation command is:01 06 00 6B 00 64 F9 FD .   

Device ID 

Function id 

Start Address 

Destination 

CRC16 

01 

06 

00 6B 

00 64 

F9 FD 

        After the operation is successful, the device will return information: 01 06 00 6B 00 64 F9 FD, the 

parameters take effect immediately after successful change. 

        Disclaimer 

Содержание SC7202B

Страница 1: ... 10 SC7202B using the standard RS485 bus MODBUS RTU protocol easy access to PLC DCS and other instruments or systems for monitoring temperature state quantities The internal use of high precision sensing core and related devices to ensure high reliability and excellent long term stability can be customized RS232 RS485 CAN 4 20mA DC0 5V 10V ZIGBEE Lora WIFI GPRS and other output methods ...

Страница 2: ...ect the cable to confirm the correctness and then use it again ID Core color Identification Note 1 Red V Power 2 Green V Power 3 Yellow A RS485 A 4 Blue B RS485 B In the case of broken wires wire the wires as shown in the figure If the product itself has no leads the core color is for reference Communication Protocol The product uses RS485 MODBUS RTU standard protocol format all operation or reply...

Страница 3: ...Code CRC16 01 03 02 55 3C 00 01 3A 79 Response should be in the data the first byte 01 indicates that the real address of the current device is 55 3C converted to decimal 20182 indicates that the current device main model is 21820 the last two bytes 00 01 Indicates that the device has a status quantity 2 Change device address For example if the current device address is 1 we want to change to 02 t...

Страница 4: ...ay value is too small we can correct it by adding 100 The command is 01 03 00 6B 00 01 F5 D6 In the command 100 is hex 0x64 If you need to reduce you can set a negative value such as 100 corresponding to the hexadecimal value of FF 9C which is calculated as 100 65535 65435 and then converted to hexadecimal to 0x FF 9C The correction value starts from 00 6B We take the first parameter as an example...

Страница 5: ...mpany makes no warranties express or implied regarding the sale and use of this product including the suitability for the specific use of the product the marketability or the infringement liability for any patent copyright or other intellectual property rights etc Product specifications and product descriptions may be modified at any time without notice Contact Us Company Shanghai Sonbest Industri...

Отзывы: