animeo IB+
4 Zone/8 Zone TouchBuco BACnet
2020/04/30
Seite 8
All drives that move as a result of local operator actions are now automatically assigned to the corre-
sponding zone. As soon as all motor controllers have been programmed, you need to complete the
procedure by clicking on OK in the "End Programming Mode" field. Use the white forward and back
arrows to select another zone and repeat the process.
H
The programming mode is enabled for a maximum of 10 minutes. Once this time has elapsed, the
motor controllers automatically exit this mode. If the time was not enough to make all necessary settings,
you can re-enable programming mode. If a motor controller was already assigned to a zone, the
previous value will be overwritten with the new programming process.
3.
"Learn not assigned Motor Controllers".
Motor controllers that have already been programmed are
excluded from assignment here. This prevents existing assignments from being overwritten by mistake.
You can tell when a motor controller is in programming mode, as the unit's LEDs run a circulating
pattern. With the Smoove UNO IB+, the LED flashes in various colors. To select this option, move the
cursor to the right (the cursor turns yellow).
Procedure 2:
Individual motor controllers are assigned via device number (ID). As such, you require the ID address of the
motor controllers. These can be found on barcode stickers on the devices themselves (example
"ID: 8390363"). With the Smoove UNO IB+, the address is printed on the rear of the front panel.
Set a check mark for the outputs of the motor controller which are to be assigned to the zone (1 – 4).
Enter the ID address of the motor controller in the field and then hit "Learn". Conversely, you can also delete
individual motor controller assignments by clicking on "Unlearn" instead of "Learn".
1.12 End Product
Once you have specified how many zones/sections are required, you now need to determine which end
product is installed on a zone-by-zone basis.
This selection must be made very accurately, as it is critical for smooth functioning of the system. For exam-
ple, if you define a Venetian blind as a roller shutter, you cannot later set up any slat turning options for this
motorized product.
The setting refers only to the zone that is shown in black on the screen. You can navigate from zone to zone
using the white forward and back arrows. Do not exit the menu until all zones have been set up. You can
also tap on the zone field (1 – 8) directly.
Selecting the end product: You can use the black forward and back arrows to navigate through the selection
list.
Selecting "Outside"/"Inside": You can narrow down the product selection by first defining whether the motor-
ized product is installed outdoors or indoors.
Selecting "Standard Motor"/"Electronic Motor": An electronic drive has different start-up behavior than a
standard drive. Taking this parameter into account improves operating ergonomics and the positioning accu-
racy of the end product/motorized product.
The following Somfy drives can be used in combination with TouchBuco and animeo IB+ motor controllers:
•
Standard Motor: LT, SLT, LS and J4 ranges (without WT designation).
•
Electronic Motor: WT range (Oximo, Ilmo, Orea) and J4 WT
If you are uncertain regarding units from certain manufacturers, please get in touch with your specialist
dealer or the actual manufacturer in question.