animeo
IB+ 2 AC MOTOR CONTROLLER . REF. 5102774 B -
8/16
CABLE
EN
A
PICTURES
[1]
2 AC Motor Controller WM 100-240 V AC,
wall mounted version
[2]
2 AC Motor Controller PCB 100-240 V AC,
PCB version (with DIN rail clip, Ref.
9008049)
B
MOUNTING
Choose the optimal location: flat and large surface
[1]
Mount the 2 AC Motor Controller WM
[2]
Mount the DIN rail version
1.
Vertical (wall mounted or PCB version)
2.
Horizontal (wall mounted version)
C
WIRING
[1]
Complete the wiring and connect power
supply
[2]
Insulated screwdriver
[3]
Wiring diagram
[4]
Check the correct running directions of the
end product
UP: the end product goes up ( C +
s
)
STOP: the end product stops ( C +
t
+
s
)
DOWN: the end product goes down ( C +
t
)
n
To close window press UP,
to open window press DOWN.
[5]
Possible switches
1.
Inteo Centralis IB, Ref. 1810138
2.
Double push button
D
CONFIGURATION
[1]
Reset / Prog button
With this button, you can access the basic
configuration of the Motor Controller.
1.
Wall mounted version
2.
PCB version
[2]
Selection of switch ergonomic
Local push button ergonomics and the type
of end products to be preselected:
• Screen mode
• Venetian blind, European mode (default
mode)
• Venetian blind, US mode
1.
To toggle between modes, press the
Reset / Prog button 2 s. Repeat until the
LED, according to the desired configura-
tion, lights up. Store by pressing 2 s.
[3]
Factory RESET
[4]
Learn running time/length
1.
Drive screen to upper end limit
2.
Press Stop until screen drives down on its
own
3.
Press Stop when lower end limit is
reached
[5]
Symbols: actions
1.
Up
2.
Stop
3.
Down
[6]
Symbols: end product status
1.
Up
2.
Upper end position
3.
Down
4.
Lower end position
m
When electronic motors are to be controlled through
this Motor Controller device it is mandatory to
configure the start-up delay time for electronic mo-
tors in the Motor Controller settings. To configure the
start-up delay time WT Setting Tool Ref. 1811242
can be used.
Connection to …
Cable
Twisted pair
Max. length
Motors
Min.:
4 x 0.75 mm
2
/18 AWG
Max.:
4 x 2.5 mm
2
/14 AWG
-
150 m
Switches
Min.:
3 x 0.6 mm/22 AWG
Max.:
3 x 2.5 mm
2
/14 AWG
Recommended
100 m
IB+ bus
Min.:
4 x 0.6 mm/22 AWG
Max.:
4 x 1.5 mm
2
/16 AWG
Recommended
1000 m
100-240 V AC
Min.:
3 x 1.5 mm
2
/16 AWG
Max.: 3 x 2.5 mm
2