11
SOC reaches the EPS restart value.
iii.
When working in this mode:
•
The max power*3 from the EPS port is limited by inverter type,
battery type and battery SOC.
•
A larger battery is always recommended for off grid / backup
configuration. You should never discharge the battery too
deeply to avoid it “Running Flat”.
•
When there is an overload or short circuit fault, the inverter will
stop working and an alarm will sound. It will try to restart
several times before shutting down completely. Turn off or
unplug load to remove the short circuit fault or overload as
soon as possible.
*2: Firmware update may be required to support this mode.
*3: Please be noted that refrigerators, air conditioners, water pumps
and etc., demand a large start up currents and may trip EPS
overload protection. Be sure not to connect too many of this kind of
load to avoid frequent system shutdown and restart.
For off-grid / back-up operating mode, one should set a
higher DischargeEndSOC@Grid value (above 50% for
example). So that there will be some energy in battery when a
grid failure occurs.